Bathroom Exhaust Fan CFM for 8 ACH

Compare eight air changes per hour with a 50 CFM intermittent bathroom exhaust example for a 720 ft³ room.

Room and air changes

Floor area × average ceiling height, in the unit selected above.

Scenario values are editable planning examples.

Measured air and filtration

Use delivered outdoor supply or exhaust. Count balanced airflow once.

Results

Example estimate
Outdoor-only fan or ERV target96 CFM
ACH airflow target 96 CFM Scenario outdoor baseline 50 CFM Existing outdoor airflow 25 CFM Added HEPA CADR 46 CFM
Added filtration assumes the outdoor baseline is met first.
Room volume
720 ft³
Room volume in metric
20.39 m³
Flow for target ACH
96 CFM
Scenario outdoor baseline
50 CFM
Added outdoor airflow for full ACH
71 CFM
Outdoor baseline still needed
25 CFM
Added particle CADR after baseline
46 CFM CADR
Existing outdoor ACH
2.08 ACH
Existing particle clean-air ACH
2.08 eACH
  • The 50 CFM intermittent exhaust example is for source removal. Check delivered flow, duct resistance and humidity control.

Worked example

A 720 ft³ bathroom needs 96 CFM for eight air changes. Compare that with the model’s 50 CFM source exhaust baseline and with the 25 CFM already delivered.

Outdoor-only fan or ERV target 96 CFM

What to check next

Measure flow at the actual grille and check duct diameter, elbows and termination. Favor good moisture extraction near the shower over simply choosing a higher nameplate CFM.

Formulas and assumptions

Air exchange
CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
Whole-dwelling baseline
62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
Outdoor flow and filtered air
Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.

Frequently asked questions

Does a 110 CFM bathroom fan always deliver eight air changes?

Delivered flow depends on the installed duct and grille. Divide measured CFM × 60 by bathroom volume to find actual air changes.

What does an undercut have to do with bathroom exhaust CFM?

An exhaust fan needs replacement air. A blocked transfer path with a closed door can reduce measured flow and increase sound.

More sizing examples

Open the general ventilation airflow calculator