Bathroom Exhaust Fan CFM for 8 ACH
Compare eight air changes per hour with a 50 CFM intermittent bathroom exhaust example for a 720 ft³ room.
Inputs
Results ↓Results
Example estimateOutdoor-only fan or ERV target96 CFM
- Room volume
- 720 ft³
- Room volume in metric
- 20.39 m³
- Flow for target ACH
- 96 CFM
- Scenario outdoor baseline
- 50 CFM
- Added outdoor airflow for full ACH
- 71 CFM
- Outdoor baseline still needed
- 25 CFM
- Added particle CADR after baseline
- 46 CFM CADR
- Existing outdoor ACH
- 2.08 ACH
- Existing particle clean-air ACH
- 2.08 eACH
- The 50 CFM intermittent exhaust example is for source removal. Check delivered flow, duct resistance and humidity control.
Calculation inputs
- Ventilation scenario
- Bathroom exhaust
- Volume unit
- Cubic feet (ft³)
- Room or dwelling volume
- 720 ft³
- Target air changes per hour
- 8 ACH
- Existing outdoor air
- 25 CFM
- Existing particle clean-air delivery
- 0 CFM CADR
Worked example
A 720 ft³ bathroom needs 96 CFM for eight air changes. Compare that with the model’s 50 CFM source exhaust baseline and with the 25 CFM already delivered.
Outdoor-only fan or ERV target 96 CFM
What to check next
Measure flow at the actual grille and check duct diameter, elbows and termination. Favor good moisture extraction near the shower over simply choosing a higher nameplate CFM.
Formulas and assumptions
- Air exchange
- CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
- Whole-dwelling baseline
- 62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
- Outdoor flow and filtered air
- Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.
Frequently asked questions
Does a 110 CFM bathroom fan always deliver eight air changes?
Delivered flow depends on the installed duct and grille. Divide measured CFM × 60 by bathroom volume to find actual air changes.
What does an undercut have to do with bathroom exhaust CFM?
An exhaust fan needs replacement air. A blocked transfer path with a closed door can reduce measured flow and increase sound.