Workshop Air Changes and Exhaust CFM
Convert a 4,800 ft³ workshop and 6 ACH to exhaust flow, then explore how existing outdoor CFM affects the remaining target.
Inputs
Results ↓Results
Example estimate- Room volume
- 4,800 ft³
- Room volume in metric
- 135.92 m³
- Flow for target ACH
- 480 CFM
- Scenario outdoor baseline
- 0 CFM
- Added outdoor airflow for full ACH
- 360 CFM
- Outdoor baseline still needed
- 0 CFM
- Added particle CADR after baseline
- 180 CFM CADR
- Existing outdoor ACH
- 1.5 ACH
- Existing particle clean-air ACH
- 3.75 eACH
- Use source capture for dust or fumes. General air changes are only a dilution estimate.
Calculation inputs
- Ventilation scenario
- Workshop dilution
- Volume unit
- Cubic feet (ft³)
- Room or dwelling volume
- 4800 ft³
- Target air changes per hour
- 6 ACH
- Existing outdoor air
- 120 CFM
- Existing particle clean-air delivery
- 180 CFM CADR
Worked example
The model compares 480 CFM of total dilution flow with measured outdoor air and particle filtration. A planer, paint area or welding station can impose very different source-control needs.
Outdoor-only fan or ERV target 480 CFM
What to check next
Use local exhaust and any required hazardous-process design. Locate clean makeup air and avoid returning contaminated exhaust to occupied spaces.
Formulas and assumptions
- Air exchange
- CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
- Whole-dwelling baseline
- 62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
- Outdoor flow and filtered air
- Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.
Frequently asked questions
Can a workshop air cleaner substitute for welding fume capture?
Use capture at the source and design for the specific contaminant. A particle CADR calculation only describes equivalent clean air for the modeled space.
Should I count the dust collector toward workshop outdoor exchange?
Only count outdoor exhaust if the air truly leaves the space. A collector that returns air indoors contributes filtration depending on its measured performance.