Workshop Air Changes and Exhaust CFM

Convert a 4,800 ft³ workshop and 6 ACH to exhaust flow, then explore how existing outdoor CFM affects the remaining target.

Room and air changes

Floor area × average ceiling height, in the unit selected above.

Scenario values are editable planning examples.

Measured air and filtration

Use delivered outdoor supply or exhaust. Count balanced airflow once.

Results

Example estimate
Outdoor-only fan or ERV target480 CFM
ACH airflow target 480 CFM Scenario outdoor baseline 0 CFM Existing outdoor airflow 120 CFM Added HEPA CADR 180 CFM
Added filtration assumes the outdoor baseline is met first.
Room volume
4,800 ft³
Room volume in metric
135.92 m³
Flow for target ACH
480 CFM
Scenario outdoor baseline
0 CFM
Added outdoor airflow for full ACH
360 CFM
Outdoor baseline still needed
0 CFM
Added particle CADR after baseline
180 CFM CADR
Existing outdoor ACH
1.5 ACH
Existing particle clean-air ACH
3.75 eACH
  • Use source capture for dust or fumes. General air changes are only a dilution estimate.

Worked example

The model compares 480 CFM of total dilution flow with measured outdoor air and particle filtration. A planer, paint area or welding station can impose very different source-control needs.

Outdoor-only fan or ERV target 480 CFM

What to check next

Use local exhaust and any required hazardous-process design. Locate clean makeup air and avoid returning contaminated exhaust to occupied spaces.

Formulas and assumptions

Air exchange
CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
Whole-dwelling baseline
62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
Outdoor flow and filtered air
Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.

Frequently asked questions

Can a workshop air cleaner substitute for welding fume capture?

Use capture at the source and design for the specific contaminant. A particle CADR calculation only describes equivalent clean air for the modeled space.

Should I count the dust collector toward workshop outdoor exchange?

Only count outdoor exhaust if the air truly leaves the space. A collector that returns air indoors contributes filtration depending on its measured performance.

More sizing examples

Open the general ventilation airflow calculator