Classroom HEPA CADR for 5 ACH
Calculate additional HEPA CADR for a classroom with existing outdoor supply and an existing portable cleaner.
Inputs
Results ↓Results
Example estimate- Room volume
- 8,100 ft³
- Room volume in metric
- 229.37 m³
- Flow for target ACH
- 675 CFM
- Scenario outdoor baseline
- 0 CFM
- Added outdoor airflow for full ACH
- 395 CFM
- Outdoor baseline still needed
- 0 CFM
- Added particle CADR after baseline
- 235 CFM CADR
- Existing outdoor ACH
- 2.07 ACH
- Existing particle clean-air ACH
- 3.26 eACH
- The clean-air target is a particle-control example. Determine occupied outdoor airflow separately.
Calculation inputs
- Ventilation scenario
- Classroom clean air
- Volume unit
- Cubic feet (ft³)
- Room or dwelling volume
- 8100 ft³
- Target air changes per hour
- 5 ACH
- Existing outdoor air
- 280 CFM
- Existing particle clean-air delivery
- 160 CFM CADR
Worked example
For 8,100 ft³, five equivalent air changes require 675 CFM of clean air. Subtract the measured 280 CFM of outdoor air and the existing 160 CFM CADR to estimate additional particle cleaning.
Outdoor-only fan or ERV target 675 CFM
What to check next
Compare settings pupils and teachers will tolerate acoustically. Use the CADR at the operating speed and ensure outdoor airflow for occupancy remains adequate.
Formulas and assumptions
- Air exchange
- CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
- Whole-dwelling baseline
- 62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
- Outdoor flow and filtered air
- Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.
Frequently asked questions
Can I add the rated CADR of two classroom filters?
You can add their delivered CADRs as an estimate for the same air zone. Place units to distribute airflow and avoid short-circuiting.
Does a classroom HEPA CADR goal address carbon dioxide?
CO₂ is controlled with outdoor air and occupancy management. Standard HEPA filtration removes particles and leaves CO₂ in the room.