ASHRAE 62.2 Example for a 1,500 ft² Home
Estimate whole-house outdoor ventilation for a three-bedroom home and compare the base CFM with a 0.35 ACH example.
Inputs
Results ↓Results
Example estimateOutdoor-only fan or ERV target75 CFM
- Room volume
- 12,750 ft³
- Room volume in metric
- 361.04 m³
- Flow for target ACH
- 74.4 CFM
- Scenario outdoor baseline
- 75 CFM
- Added outdoor airflow for full ACH
- 50 CFM
- Outdoor baseline still needed
- 50 CFM
- Added particle CADR after baseline
- 0 CFM CADR
- Existing outdoor ACH
- 0.12 ACH
- Existing particle clean-air ACH
- 0.12 eACH
- The whole-dwelling example uses the 62.2 base flow before infiltration credits and other adjustments. Confirm the adopted edition and local requirements.
Calculation inputs
- Ventilation scenario
- Residence · ASHRAE 62.2 example
- Volume unit
- Cubic feet (ft³)
- Room or dwelling volume
- 12750 ft³
- Target air changes per hour
- 0.35 ACH
- Dwelling floor area
- 1500 ft²
- Dwelling bedrooms
- 3
- Existing outdoor air
- 25 CFM
- Existing particle clean-air delivery
- 0 CFM CADR
Worked example
The dwelling has 1,500 ft² of floor area and 12,750 ft³ of volume. Calculate the bedroom-and-area base flow, then subtract the 25 CFM of measured outdoor air already available.
Outdoor-only fan or ERV target 75 CFM
What to check next
Use whole-dwelling area and an accurate bedroom count. Verify any allowed infiltration credit, delivery strategy, balancing and commissioning measurements.
Formulas and assumptions
- Air exchange
- CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
- Whole-dwelling baseline
- 62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
- Outdoor flow and filtered air
- Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.
Frequently asked questions
Does adding a fourth bedroom change the 1,500 ft² outdoor requirement?
The example adds 7.5 CFM to the baseline per added bedroom. At the same floor area, four bedrooms raise the baseline from 75 to 82.5 CFM.
Can a central fan recirculating furnace air count toward whole-house CFM?
Count measured outdoor air admitted by the system. Indoor recirculation by itself adds no outdoor flow.