ASHRAE 62.2 Example for a 1,500 ft² Home

Estimate whole-house outdoor ventilation for a three-bedroom home and compare the base CFM with a 0.35 ACH example.

Room and air changes

Floor area × average ceiling height, in the unit selected above.

Scenario values are editable planning examples.

Enter 0 for a studio. The baseline uses a minimum of one bedroom.

Measured air and filtration

Use delivered outdoor supply or exhaust. Count balanced airflow once.

Results

Example estimate
Outdoor-only fan or ERV target75 CFM
ACH airflow target 74.4 CFM Scenario outdoor baseline 75 CFM Existing outdoor airflow 25 CFM Added HEPA CADR 0 CFM
Added filtration assumes the outdoor baseline is met first.
Room volume
12,750 ft³
Room volume in metric
361.04 m³
Flow for target ACH
74.4 CFM
Scenario outdoor baseline
75 CFM
Added outdoor airflow for full ACH
50 CFM
Outdoor baseline still needed
50 CFM
Added particle CADR after baseline
0 CFM CADR
Existing outdoor ACH
0.12 ACH
Existing particle clean-air ACH
0.12 eACH
  • The whole-dwelling example uses the 62.2 base flow before infiltration credits and other adjustments. Confirm the adopted edition and local requirements.

Worked example

The dwelling has 1,500 ft² of floor area and 12,750 ft³ of volume. Calculate the bedroom-and-area base flow, then subtract the 25 CFM of measured outdoor air already available.

Outdoor-only fan or ERV target 75 CFM

What to check next

Use whole-dwelling area and an accurate bedroom count. Verify any allowed infiltration credit, delivery strategy, balancing and commissioning measurements.

Formulas and assumptions

Air exchange
CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
Whole-dwelling baseline
62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
Outdoor flow and filtered air
Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.

Frequently asked questions

Does adding a fourth bedroom change the 1,500 ft² outdoor requirement?

The example adds 7.5 CFM to the baseline per added bedroom. At the same floor area, four bedrooms raise the baseline from 75 to 82.5 CFM.

Can a central fan recirculating furnace air count toward whole-house CFM?

Count measured outdoor air admitted by the system. Indoor recirculation by itself adds no outdoor flow.

More sizing examples