Cleanroom Airflow Example at 30 ACH
Translate a 9,600 ft³ cleanroom and a 30 ACH comparison target into CFM and metric volume.
Inputs
Results ↓Results
Example estimate- Room volume
- 9,600 ft³
- Room volume in metric
- 271.84 m³
- Flow for target ACH
- 4,800 CFM
- Scenario outdoor baseline
- 0 CFM
- Added outdoor airflow for full ACH
- 4,300 CFM
- Outdoor baseline still needed
- 0 CFM
- Added particle CADR after baseline
- 1,800 CFM CADR
- Existing outdoor ACH
- 3.13 ACH
- Existing particle clean-air ACH
- 18.75 eACH
- ACH alone cannot determine an ISO class. Verify filtration, particle counts, recovery and pressure relationships.
Calculation inputs
- Ventilation scenario
- Cleanroom comparison
- Volume unit
- Cubic feet (ft³)
- Room or dwelling volume
- 9600 ft³
- Target air changes per hour
- 30 ACH
- Existing outdoor air
- 500 CFM
- Existing particle clean-air delivery
- 2500 CFM CADR
Worked example
A 9,600 ft³ room at 30 ACH corresponds to 4,800 CFM. The example includes measured outdoor air and a separate particle clean-air stream to illustrate the remaining effective delivery.
Outdoor-only fan or ERV target 4,800 CFM
What to check next
Use the cleanroom’s certification criteria, pressure cascade, occupancy, filtration and recovery testing for design. Percent outdoor air and recirculation need separate documentation.
Formulas and assumptions
- Air exchange
- CFM = volume in ft³ × ACH ÷ 60. Convert cubic meters to cubic feet by multiplying by 35.3147.
- Whole-dwelling baseline
- 62.2 example airflow = 0.03 × dwelling ft² + 7.5 × (bedrooms + 1), before adjustments. Use at least one bedroom in the equation. Bathroom and kitchen presets show example intermittent source exhaust flows.
- Outdoor flow and filtered air
- Outdoor-only sizing uses the larger of ACH flow and the scenario outdoor baseline. For particle filtration, first meet the outdoor baseline, then subtract outdoor CFM and existing CADR from target clean-air CFM.
Frequently asked questions
Does 30 air changes determine the ISO class of a cleanroom?
ISO classification uses particle concentrations under specified conditions. ACH is a design input that can help achieve the required concentration and recovery.
Why might cleanroom supply CFM far exceed outdoor supply?
Recirculated air through high-efficiency filters can provide much of the particle control. Outdoor supply serves the ventilation and pressurization needs.