Tankless Water Heater Sizing With 40°F Inlet Water
Compare tankless gas BTU and electric power for a measured 40°F winter inlet at 4.5 GPM peak hot flow.
Inputs
Results ↓Results
Example estimatePeak hot-side demand4.5 GPM
- Winter inlet temperature
- 40 °F
- Required temperature rise
- 80 °F
- Useful heat into water
- 180,000 BTU/h
- Gas input at steady efficiency
- 191,489 BTU/h
- Electric input
- 53.29 kW
- Total operating current
- 222 A
- Operating current per circuit
- 74 A
- Breaker comparison per circuit
- 80 A
- Use the manufacturer’s flow-at-rise chart and listed circuit schedule. Breaker figures here are only comparisons.
Calculation inputs
- Showers in use
- 2
- Showers hot-side flow each
- 2 GPM
- Dishwasher in use
- 0
- Dishwasher hot-side flow each
- 1 GPM
- Clothes washer in use
- 0
- Clothes washer hot-side flow each
- 1.5 GPM
- Faucets in use
- 1
- Faucets hot-side flow each
- 0.5 GPM
- Winter groundwater example
- Measured winter inlet
- Measured inlet temperature
- 40 °F
- Target heater outlet temperature
- 120 °F
- Gas efficiency basis
- Steady-state thermal efficiency
- Gas efficiency value
- 94 %
- Electric heating efficiency
- 99 %
- Electric supply voltage
- 240 V
- Equal electric circuits for comparison
- 3
Worked example
At 40°F inlet, a 120°F outlet calls for an 80°F rise. This example adds a low-flow faucet to two showers and tests the resulting winter condition against warmer inlet presets.
Peak hot-side demand 4.5 GPM
What to check next
Measure the inlet after the line has run steadily. Interior pipes can warm standing water and give a misleading winter temperature if measured immediately.
Formulas and assumptions
- Fixture flow
- Peak hot-side GPM = Σ(simultaneous fixture count × hot-side GPM each). Temperature rise = heater outlet minus winter inlet.
- Heater input
- Heat delivered to water ≈ 500 × GPM × rise in °F. Divide by steady gas efficiency for burner input, or by 3,412.14 and electric efficiency for electric kW.
- Circuit comparison
- Amps = kW × 1,000 ÷ volts for the single-phase example. Split equally among the assumed circuits and compare with the next standard breaker size. Use the manufacturer’s circuit schedule for installation.
Frequently asked questions
What happens to tankless flow when inlet water falls from 55°F to 40°F?
The lift rises from 65°F to 80°F at the same outlet. A fixed useful heat output then supports about 81% as much flow.
Is a cold-winter air temperature a substitute for tankless inlet temperature?
Use measured or utility-supplied incoming water temperature. Groundwater and buried distribution lines respond differently from outdoor air.