240 V Electric Tankless kW and Circuit Amps

Estimate electric tankless heater current at 240 V, compare an equal circuit split and review the manufacturer circuit schedule.

Simultaneous hot-water draw
Water temperature and heater

Results

Example estimate
Peak hot-side demand2.4 GPM
Showers 2.4 GPM Dishwasher 0 GPM Clothes washer 0 GPM Faucets 0 GPM
The bars include fixtures drawing hot water at the same time.
Winter inlet temperature
65 °F
Required temperature rise
55 °F
Useful heat into water
66,000 BTU/h
Gas input at steady efficiency
70,213 BTU/h
Electric input
19.54 kW
Total operating current
81.4 A
Operating current per circuit
40.7 A
Breaker comparison per circuit
45 A
  • Use the manufacturer’s flow-at-rise chart and listed circuit schedule. Breaker figures here are only comparisons.

Worked example

The example draws 2.4 GPM with a 55°F rise. The calculator reports input kW, total current and an illustrative per-circuit value if two even circuits share the load.

Peak hot-side demand 2.4 GPM

What to check next

Check service and panel capacity with a qualified installer. Use the selected model’s nameplate and listed wiring instructions for voltage, breakers, conductor ratings and circuit count.

Formulas and assumptions

Fixture flow
Peak hot-side GPM = Σ(simultaneous fixture count × hot-side GPM each). Temperature rise = heater outlet minus winter inlet.
Heater input
Heat delivered to water ≈ 500 × GPM × rise in °F. Divide by steady gas efficiency for burner input, or by 3,412.14 and electric efficiency for electric kW.
Circuit comparison
Amps = kW × 1,000 ÷ volts for the single-phase example. Split equally among the assumed circuits and compare with the next standard breaker size. Use the manufacturer’s circuit schedule for installation.

Frequently asked questions

Can I choose one breaker just by dividing tankless watts by 240?

That division estimates total operating current. Actual equipment can require several independent circuits at listed ratings and may have service-size requirements.

What should I check before using a 240 V heater on a 208 V supply?

Read the equipment rating for 208 V, including its reduced output and required circuit configuration. The modeled current assumes the entered power is delivered.