Tankless Water Heater Size for Three Showers
Check three simultaneous 2.0 GPM hot-water draws in cold weather and compare the load with a typical single gas unit.
Inputs
Results ↓Results
Example estimatePeak hot-side demand6 GPM
- Winter inlet temperature
- 42 °F
- Required temperature rise
- 78 °F
- Useful heat into water
- 234,000 BTU/h
- Gas input at steady efficiency
- 248,936 BTU/h
- Electric input
- 69.27 kW
- Total operating current
- 288.6 A
- Operating current per circuit
- 96.2 A
- Breaker comparison per circuit
- 100 A
- Use the manufacturer’s flow-at-rise chart and listed circuit schedule. Breaker figures here are only comparisons.
- The gas input estimate is above the 199,000 BTU/h comparison point. Check a larger or staged system, or reduce simultaneous demand.
Calculation inputs
- Showers in use
- 3
- Showers hot-side flow each
- 2 GPM
- Dishwasher in use
- 0
- Dishwasher hot-side flow each
- 1 GPM
- Clothes washer in use
- 0
- Clothes washer hot-side flow each
- 1.5 GPM
- Faucets in use
- 0
- Faucets hot-side flow each
- 0.6 GPM
- Winter groundwater example
- Cold US / Canadian Prairies example
- Target heater outlet temperature
- 120 °F
- Gas efficiency basis
- Steady-state thermal efficiency
- Gas efficiency value
- 94 %
- Electric heating efficiency
- 99 %
- Electric supply voltage
- 240 V
- Equal electric circuits for comparison
- 3
Worked example
Three simultaneous hot-side draws total 6.0 GPM. When winter inlet is 42°F, that can exceed the useful output of a typical single residential gas model at the required rise.
Peak hot-side demand 6 GPM
What to check next
Ask whether the three draws actually overlap and how much each uses on the hot side. Obtain manufacturer guidance for any parallel or staged heaters.
Formulas and assumptions
- Fixture flow
- Peak hot-side GPM = Σ(simultaneous fixture count × hot-side GPM each). Temperature rise = heater outlet minus winter inlet.
- Heater input
- Heat delivered to water ≈ 500 × GPM × rise in °F. Divide by steady gas efficiency for burner input, or by 3,412.14 and electric efficiency for electric kW.
- Circuit comparison
- Amps = kW × 1,000 ÷ volts for the single-phase example. Split equally among the assumed circuits and compare with the next standard breaker size. Use the manufacturer’s circuit schedule for installation.
Frequently asked questions
Can a 199,000 BTU tankless heater handle three showers in a cold climate?
Use its flow chart at the local winter rise. In the 6.0 GPM, 78°F example, water alone needs roughly 234,000 BTU/h.
How can I compare three showers that use different flow rates?
Enter the average hot-side GPM for the group or add the three rates first and model their total as a single fixture input.