Tankless Water Heater Size for Three Showers

Check three simultaneous 2.0 GPM hot-water draws in cold weather and compare the load with a typical single gas unit.

Simultaneous hot-water draw
Water temperature and heater

Results

Example estimate
Peak hot-side demand6 GPM
Showers 6 GPM Dishwasher 0 GPM Clothes washer 0 GPM Faucets 0 GPM
The bars include fixtures drawing hot water at the same time.
Winter inlet temperature
42 °F
Required temperature rise
78 °F
Useful heat into water
234,000 BTU/h
Gas input at steady efficiency
248,936 BTU/h
Electric input
69.27 kW
Total operating current
288.6 A
Operating current per circuit
96.2 A
Breaker comparison per circuit
100 A
  • Use the manufacturer’s flow-at-rise chart and listed circuit schedule. Breaker figures here are only comparisons.
  • The gas input estimate is above the 199,000 BTU/h comparison point. Check a larger or staged system, or reduce simultaneous demand.

Worked example

Three simultaneous hot-side draws total 6.0 GPM. When winter inlet is 42°F, that can exceed the useful output of a typical single residential gas model at the required rise.

Peak hot-side demand 6 GPM

What to check next

Ask whether the three draws actually overlap and how much each uses on the hot side. Obtain manufacturer guidance for any parallel or staged heaters.

Formulas and assumptions

Fixture flow
Peak hot-side GPM = Σ(simultaneous fixture count × hot-side GPM each). Temperature rise = heater outlet minus winter inlet.
Heater input
Heat delivered to water ≈ 500 × GPM × rise in °F. Divide by steady gas efficiency for burner input, or by 3,412.14 and electric efficiency for electric kW.
Circuit comparison
Amps = kW × 1,000 ÷ volts for the single-phase example. Split equally among the assumed circuits and compare with the next standard breaker size. Use the manufacturer’s circuit schedule for installation.

Frequently asked questions

Can a 199,000 BTU tankless heater handle three showers in a cold climate?

Use its flow chart at the local winter rise. In the 6.0 GPM, 78°F example, water alone needs roughly 234,000 BTU/h.

How can I compare three showers that use different flow rates?

Enter the average hot-side GPM for the group or add the three rates first and model their total as a single fixture input.

More sizing examples

Open the general tankless water heaters calculator