Tankless Water Heater Size for Two Showers
Size a tankless heater for two 2.0 GPM hot-side shower draws at a 55°F inlet and 120°F outlet.
Inputs
Results ↓Results
Example estimatePeak hot-side demand4 GPM
- Winter inlet temperature
- 55 °F
- Required temperature rise
- 65 °F
- Useful heat into water
- 130,000 BTU/h
- Gas input at steady efficiency
- 138,298 BTU/h
- Electric input
- 38.48 kW
- Total operating current
- 160.4 A
- Operating current per circuit
- 53.5 A
- Breaker comparison per circuit
- 60 A
- Use the manufacturer’s flow-at-rise chart and listed circuit schedule. Breaker figures here are only comparisons.
Calculation inputs
- Showers in use
- 2
- Showers hot-side flow each
- 2 GPM
- Dishwasher in use
- 0
- Dishwasher hot-side flow each
- 1 GPM
- Clothes washer in use
- 0
- Clothes washer hot-side flow each
- 1.5 GPM
- Faucets in use
- 0
- Faucets hot-side flow each
- 0.6 GPM
- Winter groundwater example
- Mixed US example
- Target heater outlet temperature
- 120 °F
- Gas efficiency basis
- Steady-state thermal efficiency
- Gas efficiency value
- 94 %
- Electric heating efficiency
- 99 %
- Electric supply voltage
- 240 V
- Equal electric circuits for comparison
- 3
Worked example
Two showers at 2.0 GPM each require 4.0 GPM from the heater. At 55°F inlet and 120°F outlet, compare the resulting gas input and electric load with products rated at a 65°F rise.
Peak hot-side demand 4 GPM
What to check next
Measure hot-side flow if the stated fixture rate includes cold mix. Compare with the winter utility inlet and the desired heater setpoint.
Formulas and assumptions
- Fixture flow
- Peak hot-side GPM = Σ(simultaneous fixture count × hot-side GPM each). Temperature rise = heater outlet minus winter inlet.
- Heater input
- Heat delivered to water ≈ 500 × GPM × rise in °F. Divide by steady gas efficiency for burner input, or by 3,412.14 and electric efficiency for electric kW.
- Circuit comparison
- Amps = kW × 1,000 ÷ volts for the single-phase example. Split equally among the assumed circuits and compare with the next standard breaker size. Use the manufacturer’s circuit schedule for installation.
Frequently asked questions
What tankless rating should I look for if I run two showers every morning?
Look up the heater’s delivered flow at the winter rise and compare with the hot-side peak. Headline GPM often assumes a smaller temperature rise.
Does the 2-shower requirement include a dishwasher starting at the same time?
The preset includes only showers. Add the dishwasher’s hot-water draw when its fill can coincide with the planned shower use.