Cold-Climate Mini-Split Capacity at −10°F
Estimate how much nominal mini-split capacity a small insulated room needs when its winter outdoor design temperature is −10°F.
Inputs
Results ↓Results
Example estimate- Walls and ceiling · 427 cool / 2,419 heat
- Exposed floor · 0 cool / 0 heat
- Windows and sun · 918 cool / 1,440 heat
- Outdoor air leakage · 374 cool / 1,866 heat
- People and equipment · 1,148 cool / 0 heat
- Modeled cooling load
- 2,867.5 BTU/h
- Modeled heating loss
- 5,725.6 BTU/h
- Cooling load in tons
- 0.24 tons
- Minimum nominal capacity
- 7,668.2 BTU/h
- Cold-weather capacity
- 74.7 % of nominal
- Heating output at design
- 6,720 BTU/h
- Summer / winter design
- 86°F / -10°F
- Modeled outdoor leakage
- 21.6 CFM
- The capacity curve is illustrative. Verify delivered heating capacity and operating limits for the exact model.
Calculation inputs
- Floor area
- 360 ft²
- Ceiling height
- 8 ft
- People in the room
- 2
- Room type
- Standard room
- Size for
- Heating only
- Wall perimeter facing outdoors
- 75 %
- Effective wall R-value
- 20
- Effective ceiling R-value
- 38
- Effective exposed floor R-value
- 0
- Exterior window area
- 40 ft²
- Window U-factor
- 0.45
- Main window exposure
- North
- Estimated outdoor air leakage
- 0.45 ACH
- Illustrative climate zone
- 6 · Cold
- Design temperature source
- Climate zone example
- Low-temperature capacity
- Cold-climate inverter curve
Worked example
The 360 ft² example has a tight envelope but a substantial indoor-to-outdoor temperature difference. Switch from the cold-climate curve to the typical inverter curve and compare the estimated class for the same room heat loss.
Suggested nominal class 9,000 BTU/h
What to check next
Use the manufacturer capacity ratio when data exists at −10°F. Check the minimum outdoor operating temperature, defrost behavior and available backup capacity.
Formulas and assumptions
- Envelope load
- BTU/h = Σ(area × ΔT ÷ effective R) + window area × U × ΔT. Exposed ceilings add a 10°F summer solar allowance.
- Air and internal gains
- Leakage CFM = room volume × ACH ÷ 60. Sensible airflow load uses 1.08 × CFM × ΔT. Cooling also includes 0.68 × CFM × the zone moisture difference in grains, window solar gain, people and equipment.
- Capacity and tons
- Cooling tons = cooling BTU/h ÷ 12,000. For heating, divide design heat loss by the capacity ratio. Size up to the first listed nominal class that meets the selected load.
Frequently asked questions
What is mini-split derating at −10°F?
It is the difference between nominal class and delivered heat at that temperature. Manufacturer performance tables give the actual ratio for an equipment pairing.
How do I size backup heat if the mini-split reaches its low-temperature limit?
Subtract the unit’s available heat from the design load at each relevant outdoor condition. If the unit shuts down, the backup has to cover the full load.