Cold-Climate Mini-Split Capacity at −10°F

Estimate how much nominal mini-split capacity a small insulated room needs when its winter outdoor design temperature is −10°F.

Room and use
Envelope and glazing

50% is two sides of a square room.

Use 0 if a conditioned space is above.

Use 0 to omit floor loss. Slab edges need separate modeling.

Use the whole-window rating in Btu/(h·ft²·°F).

Use natural air changes, not ACH50 from a blower-door test.

Weather and equipment

Sets example weather. Use local design temperatures when available.

Results

Example estimate
Suggested nominal class9,000 BTU/h
Cooling2,868 BTU/h 427.4 BTU/h0 BTU/h918 BTU/h374.1 BTU/h1,148 BTU/hHeating5,726 BTU/h 2,419.4 BTU/h0 BTU/h1,440 BTU/h1,866.2 BTU/h0 BTU/h
Each bar uses the same BTU/h scale.
  • Walls and ceiling · 427 cool / 2,419 heat
  • Exposed floor · 0 cool / 0 heat
  • Windows and sun · 918 cool / 1,440 heat
  • Outdoor air leakage · 374 cool / 1,866 heat
  • People and equipment · 1,148 cool / 0 heat
Modeled cooling load
2,867.5 BTU/h
Modeled heating loss
5,725.6 BTU/h
Cooling load in tons
0.24 tons
Minimum nominal capacity
7,668.2 BTU/h
Cold-weather capacity
74.7 % of nominal
Heating output at design
6,720 BTU/h
Summer / winter design
86°F / -10°F
Modeled outdoor leakage
21.6 CFM
  • The capacity curve is illustrative. Verify delivered heating capacity and operating limits for the exact model.

Worked example

The 360 ft² example has a tight envelope but a substantial indoor-to-outdoor temperature difference. Switch from the cold-climate curve to the typical inverter curve and compare the estimated class for the same room heat loss.

Suggested nominal class 9,000 BTU/h

What to check next

Use the manufacturer capacity ratio when data exists at −10°F. Check the minimum outdoor operating temperature, defrost behavior and available backup capacity.

Formulas and assumptions

Envelope load
BTU/h = Σ(area × ΔT ÷ effective R) + window area × U × ΔT. Exposed ceilings add a 10°F summer solar allowance.
Air and internal gains
Leakage CFM = room volume × ACH ÷ 60. Sensible airflow load uses 1.08 × CFM × ΔT. Cooling also includes 0.68 × CFM × the zone moisture difference in grains, window solar gain, people and equipment.
Capacity and tons
Cooling tons = cooling BTU/h ÷ 12,000. For heating, divide design heat loss by the capacity ratio. Size up to the first listed nominal class that meets the selected load.

Frequently asked questions

What is mini-split derating at −10°F?

It is the difference between nominal class and delivered heat at that temperature. Manufacturer performance tables give the actual ratio for an equipment pairing.

How do I size backup heat if the mini-split reaches its low-temperature limit?

Subtract the unit’s available heat from the design load at each relevant outdoor condition. If the unit shuts down, the backup has to cover the full load.

More sizing examples

Open the general mini-split sizing calculator