Radiant Floor GPM at 10°F vs. 20°F ΔT
Compare total and per-loop radiant flow for 34,000 BTU/h at a 10°F or 20°F supply-to-return temperature drop.
Inputs
Results ↓Results
Example estimate- Balanced loop length
- 292 ft
- Balanced circuits
- 7 loops
- Manifold supply/return pairs
- 7 ports
- Active tubing before tails
- 1,904 ft
- Supply and return tails per loop
- 20 ft
- Design floor load
- 34,000 BTU/h
- Total manifold flow
- 6.8 GPM
- Flow per loop
- 0.97 GPM
- Modeled tubing velocity
- 1.76 ft/s
- Tubing and assumed ID
- PEX-A · 0.475 in ID
- Verify tubing ID, bend radius, oxygen barrier, floor output and pump head for the installed system.
Calculation inputs
- Net heated floor area
- 1360 ft²
- Tube spacing on center
- 9 in
- Nominal tubing size
- ½ in
- PEX type
- PEX-A
- Routing allowance
- 5 %
- Manifold distance per circuit
- 10 ft
- Maximum total circuit length
- 300 ft
- Design floor heat load
- 25 BTU/h·ft²
- Supply-to-return temperature drop
- 10 °F
Worked example
The floor has a 34,000 BTU/h design load. At 10°F drop it needs 6.8 GPM of water. At 20°F the same load requires about 3.4 GPM, while the circuit count stays tied to geometry.
Total tubing including tails 2,044 ft
What to check next
Verify supply water temperature, surface temperature and allowable across-floor temperature difference with the selected assembly. Pump selection also needs the critical loop’s head loss.
Formulas and assumptions
- Active tube
- Active footage = floor area × 12 ÷ spacing in inches × (1 + routing allowance).
- Balanced circuits
- Circuit count = round up(active footage ÷ (loop limit − two manifold tails)). Balanced length = active footage ÷ circuits + tails.
- Water flow
- GPM = BTU/h ÷ (500 × supply-return ΔT). Divide system flow by the number of equally loaded circuits. The velocity uses representative tubing ID.
Frequently asked questions
Does a larger hydronic ΔT reduce per-loop GPM by the same proportion?
With the same water and load, doubling ΔT halves total flow and each balanced loop’s share. Check floor output and comfort at the new operating temperatures.
Why does the radiant calculator use 500 in the water flow formula?
The rounded constant combines water density, specific heat and 60 minutes per hour. Glycol mixtures require a different fluid factor.