BTU sizing for a 10×12 twin-wall greenhouse at 20°F

The gabled house is 10 ft wide and 12 ft long, with 6 ft eaves and a 2 ft roof rise. The inside target is 60°F at a 20°F outdoor design temperature.

Inputs

Exposed envelope
ft
ft
ft
ft
Design conditions
°F
°F
×

Use 1.00 for conduction only.

Results

Estimated heat output

11,717 BTU/hr

Glazing loss adjusted by the exposure multiplier

Exposed glazing area
413.24 ft²
Heating temperature difference
40 °F
Glazing U-value
3.5 W/m²·K
Conduction before wind factor
2.99 kW
Estimated load
11,717 BTU/hr
Estimated load
3.43 kW

Glazing comparison

Same envelope, temperature difference and exposure for each material.

Heat output by glazing materialTwin-wall polycarbonate: 11,717.01 BTU/hr. Single glass: 20,755.85 BTU/hr. Double poly film: 13,390.87 BTU/hr. Single poly film: 22,764.48 BTU/hrTwin-wall polycarbonate11,717 BTU/hrSingle glass20,756 BTU/hrDouble poly film13,391 BTU/hrSingle poly film22,764 BTU/hr

Worked calculation

  1. Find the exposed envelope

    2 × (12 + 10) × 6 + 10 × 2 + 2 × 12 × √((10 ÷ 2)² + 2²) = 413.24 ft²

  2. Find the positive temperature difference

    max(0, 15.56 − (-6.67)) = 22.22 °C

  3. Apply the U-value and exposure multiplier

    3.5 × 38.392 m² × 22.222 K × 1.15 = 3,433.9 W

  4. Convert watts into BTU/hr

    3,433.9 × 3.41214 = 11,717 BTU/hr

What the example shows

The exposed area is about 413 ft². With a 3.5 W/m²·K U-value and a 1.15 exposure factor, this model estimates about 11,717 BTU/hr.

How the model works

The estimate uses U × area × temperature difference. The envelope covers roofs, walls and closed ends. The ground plane is outside this geometry model. A semicircular hoop uses radius equal to half the width.

Preset U-values are representative. Check the glazing assembly’s published U-value. Exposure is an allowance, and a full equipment sizing calculation also accounts for infiltration, ground losses, radiation and heater efficiency.

References

Common questions

Why is the glazing area much larger than the 120 ft² floor?

The envelope includes two sidewalls, two gable ends and two roof slopes. The floor footprint measures the level ground beneath them.

Will a 12,000 BTU/hr heater necessarily hold 60°F in the 10×12 house?

Check the delivered output, local design temperature and air leakage. A small difference between heater output and modeled loss can disappear once those are included.