Heating kW for a 4 × 8 m double-polythene greenhouse

A 4×8 m double-polythene house has 2 m eaves and a 1 m rise. Its setpoint is 18°C, outside design is −6°C and the exposure factor is 1.25.

Inputs

Exposed envelope
m
m
m
m
Design conditions
°C
°C
×

Use 1.00 for conduction only.

Results

Estimated heat output

10.53 kW

Glazing loss adjusted by the exposure multiplier

Exposed glazing area
87.78 m²
Heating temperature difference
24 °C
Glazing U-value
4 W/m²·K
Conduction before wind factor
8.43 kW
Estimated load
35,941 BTU/hr
Estimated load
10.53 kW

Glazing comparison

Same envelope, temperature difference and exposure for each material.

Heat output by glazing materialTwin-wall polycarbonate: 9.22 kW. Single glass: 16.33 kW. Double poly film: 10.53 kW. Single poly film: 17.91 kWTwin-wall polycarbonate9.22 kWSingle glass16.33 kWDouble poly film10.53 kWSingle poly film17.91 kW

Worked calculation

  1. Find the exposed envelope

    2 × (8 + 4) × 2 + 4 × 1 + 2 × 8 × √((4 ÷ 2)² + 1²) = 87.78 m²

  2. Find the positive temperature difference

    max(0, 18 − (-6)) = 24 °C

  3. Apply the U-value and exposure multiplier

    4 × 87.777 m² × 24 K × 1.25 = 10,533.3 W

  4. Convert watts into BTU/hr

    10,533.3 × 3.41214 = 35,940.9 BTU/hr

What the example shows

The envelope is roughly 87.78 m², which gives 10.53 kW under the example assumptions. Review the stated heat output of any proposed heater.

How the model works

The estimate uses U × area × temperature difference. The envelope covers roofs, walls and closed ends. The ground plane is outside this geometry model. A semicircular hoop uses radius equal to half the width.

Preset U-values are representative. Check the glazing assembly’s published U-value. Exposure is an allowance, and a full equipment sizing calculation also accounts for infiltration, ground losses, radiation and heater efficiency.

References

Common questions

Is a 24°C temperature difference also 24 K?

Yes. Celsius and kelvin use the same interval size. A temperature difference of 24°C equals 24 K in the heat-loss equation.

How do I compare 10.53 kW of heat with the heater’s fuel use?

Divide required output by appliance efficiency to estimate thermal fuel input. Use measured operating hours and the fuel’s stated energy content for consumption.