Heating kW for a 4 × 8 m double-polythene greenhouse
A 4×8 m double-polythene house has 2 m eaves and a 1 m rise. Its setpoint is 18°C, outside design is −6°C and the exposure factor is 1.25.
Inputs
Results
Estimated heat output
Glazing loss adjusted by the exposure multiplier
- Exposed glazing area
- 87.78 m²
- Heating temperature difference
- 24 °C
- Glazing U-value
- 4 W/m²·K
- Conduction before wind factor
- 8.43 kW
- Estimated load
- 35,941 BTU/hr
- Estimated load
- 10.53 kW
Glazing comparison
Same envelope, temperature difference and exposure for each material.
Inputs used
- Greenhouse shape
- Gable roof
- Greenhouse length
- 8 m
- Greenhouse width
- 4 m
- Sidewall height
- 2 m
- Roof rise above sidewall
- 1 m
- Indoor design temperature
- 18 °C
- Outdoor design temperature
- -6 °C
- Glazing
- Double poly film
- Wind and exposure factor
- 1.25 ×
Worked calculation
- Find the exposed envelope
2 × (8 + 4) × 2 + 4 × 1 + 2 × 8 × √((4 ÷ 2)² + 1²) = 87.78 m²
- Find the positive temperature difference
max(0, 18 − (-6)) = 24 °C
- Apply the U-value and exposure multiplier
4 × 87.777 m² × 24 K × 1.25 = 10,533.3 W
- Convert watts into BTU/hr
10,533.3 × 3.41214 = 35,940.9 BTU/hr
What the example shows
The envelope is roughly 87.78 m², which gives 10.53 kW under the example assumptions. Review the stated heat output of any proposed heater.
How the model works
The estimate uses U × area × temperature difference. The envelope covers roofs, walls and closed ends. The ground plane is outside this geometry model. A semicircular hoop uses radius equal to half the width.
Preset U-values are representative. Check the glazing assembly’s published U-value. Exposure is an allowance, and a full equipment sizing calculation also accounts for infiltration, ground losses, radiation and heater efficiency.
References
Common questions
Is a 24°C temperature difference also 24 K?
Yes. Celsius and kelvin use the same interval size. A temperature difference of 24°C equals 24 K in the heat-loss equation.
How do I compare 10.53 kW of heat with the heater’s fuel use?
Divide required output by appliance efficiency to estimate thermal fuel input. Use measured operating hours and the fuel’s stated energy content for consumption.