Greenhouse heat loss from 240 ft² and a rated U-value

An envelope takeoff gives 240 ft² of exposed glazing with a rated U-factor of 0.50 BTU/hr·ft²·°F. The inside and outside design temperatures are 65°F and 25°F.

Inputs

Exposed envelope
ft²
Design conditions
°F
°F
BTU/hr·ft²·°F
×

Use 1.00 for conduction only.

Results

Estimated heat output

5,280 BTU/hr

Glazing loss adjusted by the exposure multiplier

Exposed glazing area
240 ft²
Heating temperature difference
40 °F
Glazing U-value
2.84 W/m²·K
Conduction before wind factor
1.41 kW
Estimated load
5,280 BTU/hr
Estimated load
1.55 kW

Glazing comparison

Same envelope, temperature difference and exposure for each material.

Heat output by glazing materialTwin-wall polycarbonate: 6,509.03 BTU/hr. Single glass: 11,530.29 BTU/hr. Double poly film: 7,438.89 BTU/hr. Single poly film: 12,646.12 BTU/hr. Custom U-value: 5,280 BTU/hrTwin-wall polycarbonate6,509 BTU/hrSingle glass11,530 BTU/hrDouble poly film7,439 BTU/hrSingle poly film12,646 BTU/hrCustom U-value5,280 BTU/hr

Worked calculation

  1. Find the exposed envelope

    Entered glazing area = 240 ft²

  2. Find the positive temperature difference

    max(0, 18.33 − (-3.89)) = 22.22 °C

  3. Apply the U-value and exposure multiplier

    2.839 × 22.297 m² × 22.222 K × 1.1 = 1,547.4 W

  4. Convert watts into BTU/hr

    1,547.4 × 3.41214 = 5,280 BTU/hr

What the example shows

The base load is 4,800 BTU/hr. A 1.10 exposure multiplier gives 5,280 BTU/hr, which makes the manual-area formula easy to check by hand.

How the model works

The estimate uses U × area × temperature difference. The envelope covers roofs, walls and closed ends. The ground plane is outside this geometry model. A semicircular hoop uses radius equal to half the width.

Preset U-values are representative. Check the glazing assembly’s published U-value. Exposure is an allowance, and a full equipment sizing calculation also accounts for infiltration, ground losses, radiation and heater efficiency.

References

Common questions

Can I enter a product R-value of 2 directly in the custom U field?

Use its reciprocal in compatible units. An R-value of 2 hr·ft²·°F/BTU corresponds to U = 0.5 BTU/hr·ft²·°F.

Should the 240 ft² include both sides of each glazing panel?

Use the area of each assembly once. U relates heat flow through the panel to the temperature difference across it.