Warehouse pallet storage LPD
Check the connected watts in a medium-to-bulky palletized storage space with long annual operating hours.
Inputs
View results ↑- Actual LPD
- 0.354W/ft²
- LPD margin
- -7.4%
- Energy saved
- 30,613kWh/yr
- Payback
- 5.3yr
Installed power and allowance
Edit inputs ↓Connected LPD screen
Review needed- Connected power density0.35 / ≤ 0.33 W/ft² outside screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Additional readings
| Selected LPD allowance | 0.33W/ft² |
|---|---|
| Connected load | 6,380W |
| Connected power allowance | 5,940W |
| Allowance minus connected load | -440W |
| Equivalent controlled load | 4,785W |
| Legacy lighting energy | 52,624kWh/yr |
| Post-retrofit lighting energy | 22,011kWh/yr |
| Annual utility savings | 3,673.56USD/yr |
Worked calculation
US customary results for the original preset.
- Divide 6380 W of connected load by 18000 ft² to get 0.354 W/ft². The selected limit is 0.33 W/ft².
- After applying the control credit to annual use, compare 52624 kWh/yr before retrofit with 22011 kWh/yr after retrofit.
- At 0.12 USD/kWh, the annual cost difference is 3673.56 USD/yr. Simple payback is 5.34 yr.
Calculation method
Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.
- Connected lighting power density
- LPD = fixture count × input watts/floor area
- Annual energy savings
- ΔkWh = (legacy watts − installed watts × (1 − control credit)) × hours/1000
- Simple payback
- Years = retrofit cost/(ΔkWh × utility rate), when savings are positive
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.
Sources and assumptions ↗Warehouse pallet storage LPD
Inputs
| Space type | Warehouse · palletized storage |
|---|---|
| Lighted floor area | 18,000ft² |
| Fixture count | 44 |
| Installed watts per fixture | 145W |
| Control energy credit | 25% |
| Operating hours | 4,600h/yr |
| Legacy watts per fixture | 260W |
| Electricity rate | 0.12USD/kWh |
| Retrofit capital cost | 19,600USD |
Results
| Actual LPD | 0.354W/ft² |
|---|---|
| LPD margin | -7.4% |
| Energy saved | 30,613kWh/yr |
| Payback | 5.3yr |
| Selected LPD allowance | 0.33W/ft² |
| Connected load | 6,380W |
| Connected power allowance | 5,940W |
| Allowance minus connected load | -440W |
| Equivalent controlled load | 4,785W |
| Legacy lighting energy | 52,624kWh/yr |
| Post-retrofit lighting energy | 22,011kWh/yr |
| Annual utility savings | 3,673.56USD/yr |
Connected LPD screen
- Connected power density · 0.35 / ≤ 0.33 W/ft² · Outside screen
Comparison uses the 90.1-2019 Space-by-Space base allowance without control credits.
Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.