Worked example · Deck foundations
40 ft² Deck Footing on 2,500 psf Soil at 48 Inches
A low 6×6 post serves 5 ft by 8 ft of deck. The entered soil value falls halfway between the 2,000 and 3,000 psf columns. Enter a 48 in. local bottom-depth requirement.
Example inputs
Worked result
Updates as you type- Gravity load per post
- 2,000 lb
- Rounded footing diameter screen
- 14 in
- IRC Southern Pine post height
- 14 ft
Tributary area and pier section
SchematicProject inputs
- Tributary width
- 5 ft
- Tributary length
- 8 ft
- Unbraced post height
- 5 ft
- Southern Pine post
- 6 × 6 nominal
- Ground snow load
- 0 psf
- Allowable soil bearing
- 2,500 psf
- Local footing bottom depth
- 48 in
- Selected pier diameter
- 0 in
- Identical piers to pour
- 3
- Effective length factor K
- 1
- Adjusted compression Fc*
- 900 psi
- Adjusted minimum E′min
- 450,000 psi
Calculation details
- Gravity load per post
- 2,000 lb
- Rounded footing diameter screen
- 14 in
- IRC Southern Pine post height
- 14 ft
- Post tributary area
- 40 ft²
- Modeled axial column capacity
- 25,353 lb
- Column slenderness Le/d
- 10.9
- Column stability Cp
- 0.931
- R507.3.1 round footing minimum
- 13 in
- R507.3.1 plain footing thickness
- 6 in
- Diameter for entered soil capacity
- 13.89 in
- Modeled pier diameter
- 14 in
- Gross soil pressure
- 2,471 psf
- Pier bottom below grade
- 48 in
- Concrete per full-depth pier
- 4.276 ft³
- Concrete across all piers
- 0.475 yd³
Checks and references
- Within limit
R507.4 post height
The table screen assumes Southern Pine No. 2 in wet service. Measure from footing top to beam underside.
- Within limit
Axial column stability
The NDS-style stability screen uses K = 1, Le/d ≤ 50 and the adjusted properties entered. Confirm actual restraint and combined loading.
- Within limit
R507.3.1 round footing
The 2021 IRC screen uses the next applicable load band and interpolates within table areas and soil values.
- Within limit
Bearing and post fit
Gross pressure includes 150 lb/ft³ concrete. The footing must support the full square post footprint. Check anchor edge distances separately.
- Reference
Frost protection
Footing bottoms use the larger of 12 in. and the entered local requirement. Confirm frost protection, site soil and footing detail with the local authority.
Worked calculation
The steps use US customary units for the reference formulas.
Find the post tributary load
5 ft × 8 ft = 40 ft². Multiply by 10 psf dead plus the larger of 40 psf live and ground snow for 2,000 lb.
Screen the post as a column
Use effective length K × height and a 5.5 in actual side. Le/d = 10.91. Apply the column stability factor Cp = 0.931 to the adjusted compression stress.
Check the footing diameter
Use R507.3.1 and the entered soil capacity. For the gross-pressure screen, divide post load by soil capacity less the pier self-weight per square foot, then solve the circle area for diameter.
Estimate the pier concrete
A 14 in diameter cylinder to 48 in below grade holds 4.28 ft³ per pier and yields 2,471 psf gross bearing pressure.
Enter valid values to see the steps for this layout.
Frequently asked questions
How is the 2,500 psf round-footing table value obtained at 40 ft²?
The two bounding round diameters are 14 in. at 2,000 psf and 12 in. at 3,000 psf. Interpolation at the midpoint gives 13 in.
How does a 48 in. full-depth cylinder affect the pressure margin?
At 150 lb/ft³, the cylinder adds 600 psf before the post load is applied.