Wall Dew Point & Sheathing Condensation Calculator
Compare the indoor dew point to the temperature at the inside face of the sheathing. Estimate the exterior insulation needed for the selected winter conditions.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Sheathing temperature
- °F
- Indoor dew point
- °F
- Margin above dew point
- °F
Condensation risk at the sheathing if exposed to indoor air under these conditions.
Temperature through the wall
- Exterior foam R at dew-point threshold
- R
- Total cavity-path R
- R
- R inboard of sheathing
- R
Inputs used
- Indoor temperature
- 70 °F
- Indoor relative humidity
- 40 %
- Outdoor temperature
- 15 °F
- Interior film and finish R
- 1.1 R
- Cavity insulation R
- 20 R
- Sheathing, exterior film and other outboard R
- 0.8 R
- Continuous exterior foam R
- 7.5 R
How this calculation works
The Magnus equation estimates indoor dew point from indoor temperature and relative humidity. The interface temperature is T_inside − (T_inside − T_outside) × R_inboard ÷ R_total.
The calculator solves for the exterior foam R where the interface just reaches the indoor dew point. The result is a threshold for this one set of conditions. A practical assembly needs a margin and a documented plan for drying.
This is a steady-state cavity-path screen for exposure to indoor air. It omits vapor diffusion, rain, solar heating, heat storage, moisture buffering, framing effects and summertime inward vapor drive.
References
Frequently asked questions
Which face of the sheathing is the calculator checking?
It checks the inside face of the exterior sheathing, where the cavity path meets the first outboard layer. Put the sheathing, exterior film and other outboard layers into the exterior-side inputs.
Why does more cavity R sometimes make winter sheathing colder?
With outdoor conditions and exterior R held fixed, more cavity R causes a greater fraction of the temperature drop to occur before the sheathing.