Worked example
A Bath-House Wall at 100% Indoor RH
A bath-house screening run uses saturated 80°F indoor air and a 32°F outdoor condition. Equal R on both sides of the interface places the sheathing at the midpoint of the temperature difference.
Try it Reduce indoor RH from 100% to 65% to see why humidity control matters when the indoor space starts near saturation.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Sheathing temperature
- °F
- Indoor dew point
- °F
- Margin above dew point
- °F
Condensation risk at the sheathing if exposed to indoor air under these conditions.
Temperature through the wall
- Exterior foam R at dew-point threshold
- Total cavity-path R
- R
- R inboard of sheathing
- R
Inputs used
- Indoor temperature
- 80 °F
- Indoor relative humidity
- 100 %
- Outdoor temperature
- 32 °F
- Interior film and finish R
- 1 R
- Cavity insulation R
- 11 R
- Sheathing, exterior film and other outboard R
- 1 R
- Continuous exterior foam R
- 11 R
How this calculation works
The Magnus equation estimates indoor dew point from indoor temperature and relative humidity. The interface temperature is T_inside − (T_inside − T_outside) × R_inboard ÷ R_total.
The calculator solves for the exterior foam R where the interface just reaches the indoor dew point. The result is a threshold for this one set of conditions. A practical assembly needs a margin and a documented plan for drying.
This is a steady-state cavity-path screen for exposure to indoor air. It omits vapor diffusion, rain, solar heating, heat storage, moisture buffering, framing effects and summertime inward vapor drive.
References
Frequently asked questions
Why is there no finite foam threshold for this saturated bath-house wall?
At 100% RH, indoor dew point equals indoor air temperature. With colder outdoor air and positive inboard resistance, any finite exterior R leaves some temperature drop before the sheathing.
Where should I measure humidity for an intermittently occupied bath house?
Take readings during a representative period of use and after operation of the ventilation system. Use both conditions to see how rapidly the dew point target changes.