Worked example
Heated Garage Wall with No Continuous Foam
A detached garage stays near 60°F and sees 15°F outdoors. A partially insulated wall provides R-9 on the inside of the sheathing and only R-1 outside the interface.
Try it Set the foam R to 5, then test a wetter indoor condition to represent bringing a snow-covered vehicle inside.
Results
Back to inputs ↑Enter valid inputs to calculate results and draw the diagram.
- Sheathing temperature
- °F
- Indoor dew point
- °F
- Margin above dew point
- °F
Condensation risk at the sheathing if exposed to indoor air under these conditions.
Temperature through the wall
- Exterior foam R at dew-point threshold
- R
- Total cavity-path R
- R
- R inboard of sheathing
- R
Inputs used
- Indoor temperature
- 60 °F
- Indoor relative humidity
- 45 %
- Outdoor temperature
- 15 °F
- Interior film and finish R
- 1 R
- Cavity insulation R
- 8 R
- Sheathing, exterior film and other outboard R
- 1 R
- Continuous exterior foam R
- 0 R
How this calculation works
The Magnus equation estimates indoor dew point from indoor temperature and relative humidity. The interface temperature is T_inside − (T_inside − T_outside) × R_inboard ÷ R_total.
The calculator solves for the exterior foam R where the interface just reaches the indoor dew point. The result is a threshold for this one set of conditions. A practical assembly needs a margin and a documented plan for drying.
This is a steady-state cavity-path screen for exposure to indoor air. It omits vapor diffusion, rain, solar heating, heat storage, moisture buffering, framing effects and summertime inward vapor drive.
References
Frequently asked questions
How could a wet vehicle affect the heated garage reading?
Evaporating water can raise indoor humidity. A higher dew point makes the same interior-facing sheathing temperature more likely to be below the threshold.
Should I enter R-0 for every outboard layer in the garage?
Enter zero for the absent foam. Keep the resistance of the sheathing, exterior film and relevant remaining layers.