Marine-Climate Wall with Exterior EPS

A crew plans a marine-climate siding retrofit with R-9 of exterior EPS. The inside is 68°F and 50% RH, the outdoor check is 40°F, and the cavity-plus-interior path is R-15.

Try it Reduce the exterior foam to R-5 in the calculator and compare the margin above dew point to the full R-9 design.

Air conditions
°F
%
°F
Insulation and layers
R
R
R
R

The interface is the indoor-facing side of the sheathing.

Sheathing temperature
51.2 °F
Indoor dew point
48.7 °F
Margin above dew point
2.5 °F

The sheathing is above indoor dew point by less than 3°F (1.7 K). Small changes can use up that margin.

Temperature through the wall

Temperature and indoor dew point through the wallIndoor dew point 48.7 °F. Sheathing 51.2 °F. 3545546473°FWall temperatureIndoor dew pointInsideOutsideCumulative resistanceSheathing 51.2 °F
Horizontal position follows cumulative thermal resistance. The dashed line is the indoor dew point.
Exterior foam R at dew-point threshold
5.73 R
Total cavity-path R
25 R
R inboard of sheathing
15 R
Download

How this calculation works

The Magnus equation estimates indoor dew point from indoor temperature and relative humidity. The interface temperature is T_inside − (T_inside − T_outside) × R_inboard ÷ R_total.

The calculator solves for the exterior foam R where the interface just reaches the indoor dew point. The result is a threshold for this one set of conditions. A practical assembly needs a margin and a documented plan for drying.

This is a steady-state cavity-path screen for exposure to indoor air. It omits vapor diffusion, rain, solar heating, heat storage, moisture buffering, framing effects and summertime inward vapor drive.

References

Frequently asked questions

Why check a 40°F day for a marine-climate retrofit?

Long stretches near that condition can be relevant to winter moisture exposure. Run additional cases for local design conditions and expected indoor humidity.

Does the EPS wall result account for rain behind the siding?

Rain entry and drainage are separate moisture loads. The modeled EPS value only affects the temperature profile, so check the drainage plane and detailing independently.