WaterTreatLab

Chemical feed / Worked example

Diluted Polymer Metering at 0.75 MGD

Size pump flow for a 0.5% active polymer solution delivering a 0.8 mg/L active dose to 0.75 MGD.

Inputs

Process & solution
mg/L
%
Mass percent (w/w)
Pump & inventory
gph
gal
gal

Results

US customary
Liquid feed
4.8544 gph 306.26 mL/min
Active chemical
5.004 lb/d 2.2698 kg/d
Pump capacity used
48.544 %
Day-tank autonomy
0.85833 d
Chemical metering circuitLive diagram
Chemical metering circuitThe day-tank fill shows remaining stock after 24 hours from a full tank. Day-tank autonomy0.85833 dLiquid stock feed4.8544 gphMetering pumpProcess mainRequired pump output48.544 %10%90%
The day-tank fill shows remaining stock after 24 hours from a full tank.
Bulk-tank autonomy
8.5833 d
Dose target
0.8 mg/L
Dose at rated flow
1.648 mg/L
Stock used per day
116.5 gal/d

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. The 0.75 MGD process needs 5.004 lb/day of active polymer.
  2. At 0.5% w/w and 1.03 SG, 5.004 ÷ (24 × 8.34 × 1.03 × 0.005) gives 4.85 gph of diluted stock.

More worked examples

Hypochlorite Feed at 2 MGD

Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.

Equations & conventions

Active mass rate
W = 8.34 × Qₘɢᴅ × D

Q is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.

Liquid feed rate
q = W / (24 × 8.34 × SG × w)

w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.

Capacity and inventory
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)

Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.

Planning basis

The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.

Questions

Which strength applies after a polymer make-down step?

Enter the active mass percentage and density of the liquid the metering pump actually draws.