WaterTreatLab

Chemical feed / Worked example

Hypochlorite Feed at 2 MGD

Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.

Inputs

Process & solution
mg/L
%
Mass percent (w/w)
Pump & inventory
gph
gal
gal

Results

US customary
Liquid feed
1.6667 gph 105.15 mL/min
Active chemical
50.04 lb/d 22.698 kg/d
Pump capacity used
41.667 %
Day-tank autonomy
0.875 d
Chemical metering circuitLive diagram
Chemical metering circuitThe day-tank fill shows remaining stock after 24 hours from a full tank. Day-tank autonomy0.875 dLiquid stock feed1.6667 gphMetering pumpProcess mainRequired pump output41.667 %10%90%
The day-tank fill shows remaining stock after 24 hours from a full tank.
Bulk-tank autonomy
8.75 d
Dose target
3 mg/L
Dose at rated flow
7.2 mg/L
Stock used per day
40 gal/d

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. A 3 mg/L dose at 2 MGD requires 8.34 × 2 × 3 = 50.04 lb/day active chemical.
  2. At 12.5% w/w and SG 1.20, each gallon contains 1.251 lb active. Divide the load by 1.251 × 24 for 1.667 gph.
  3. A 4 gph head runs at an equivalent 41.67% capacity. At 40 gal/day, 35 usable gal lasts 0.875 day.

More worked examples

Equations & conventions

Active mass rate
W = 8.34 × Qₘɢᴅ × D

Q is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.

Liquid feed rate
q = W / (24 × 8.34 × SG × w)

w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.

Capacity and inventory
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)

Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.

Planning basis

The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.

Questions

How long would the 350 gal bulk inventory last in this example?

The modeled draw is 40 gal/day, so a separate 350 usable gal supply lasts 8.75 days.