WaterTreatLab

Chemical feed / Worked example

Peak Dose Above Pump Capacity

Compare a requested 8 mg/L active dose with what an 8 gph pump can meet at peak process flow.

Inputs

Process & solution
mg/L
%
Mass percent (w/w)
Pump & inventory
gph
gal
gal

Results

US customary
Liquid feed
11.799 gph 744.43 mL/min
Active chemical
266.88 lb/d 121.05 kg/d
Pump capacity used
147.49 %
Day-tank autonomy
0.26484 d
Chemical metering circuitLive diagram
Chemical metering circuitThe day-tank fill shows remaining stock after 24 hours from a full tank. Day-tank autonomy0.26484 dLiquid stock feed11.799 gphMetering pumpProcess mainRequired pump output147.49 %10%90%
The day-tank fill shows remaining stock after 24 hours from a full tank.
Review the operating point
  • Required feed exceeds the rated pump capacity.
Bulk-tank autonomy
1.9422 d
Dose target
8 mg/L
Dose at rated flow
5.424 mg/L
Stock used per day
283.19 gal/d

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. The target requires 266.88 lb/day active and about 11.80 gph of the entered stock.
  2. At 8 gph the pump can provide about 5.424 mg/L at this flow. The target would require about 147.5% rated output.

More worked examples

Hypochlorite Feed at 2 MGD

Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.

Equations & conventions

Active mass rate
W = 8.34 × Qₘɢᴅ × D

Q is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.

Liquid feed rate
q = W / (24 × 8.34 × SG × w)

w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.

Capacity and inventory
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)

Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.

Planning basis

The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.

Questions

Does the capacity warning change the calculated liquid demand?

The target still calls for 11.80 gph. The rated-dose output shows the max available from the entered pump and stock.