Chlorine CT, Baffling Factor & Breakpoint Calculator

Calculate theoretical contact time, EPA T₁₀, achieved chlorine CT and the ratio to your target. Screen ammonia breakpoint demand.

Inputs

Contact segment
mg/L
gal
gpm
mg·min/L
Breakpoint screen
mg/L as N
mg/L as Cl₂

Results

US customary
Achieved CT
58.8 mg·min/L
Effective time T₁₀
42 min
CT / target
1.0691 ×
Theoretical time T
60 min
Contact basinLive diagram
Contact basinFlow path and effective contact time for the selected baffling class. InletOutlet residualBaffling factor 0.7Theoretical time60 minEffective T₁₀42 minCT / target1.0691 ×
Flow path and effective contact time for the selected baffling class.
Breakpoint demand
2.5 mg/L as Cl₂
Dose incl. entered residual
3.9 mg/L as Cl₂

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked examples

Equations & conventions

Theoretical and effective time
T = V / Q, T₁₀ = T × BF

Use operating volume and peak flow for the same segment. EPA Table 4-2 uses 0.1, 0.3, 0.5, 0.7 and 1.0 for progressively improved baffling. Use approved tracer results when available.

Disinfection exposure
CT = C × T₁₀, CT ratio = CT / CTrequired

C is the measured disinfectant residual at the end of the segment. Use the applicable required CT for the disinfectant, organism, inactivation goal, temperature and pH.

Theoretical breakpoint
Dᵦ = 7.6 × ammonia-N + other demand

Express ammonia as N and chlorine as Cl₂. The optional residual allowance is added separately. Determine actual breakpoint from site demand testing and approved operating procedures.

Planning basis

A CT ratio at or above one means the calculated value meets your entered target for this segment. A regulated inactivation determination also requires the governing method, sampling, operating envelope and any segment accounting.

Questions

Which chlorine value belongs in the CT formula?

Use the measured residual of the relevant disinfectant at the segment outlet. Applied dose includes chlorine that was consumed by demand before reaching that point.

How do I choose the required CT target?

Use the applicable authority’s CT table with disinfectant type, target organism, desired log inactivation, minimum temperature and relevant pH and residual.