WaterTreatLab

Disinfection / Worked example

Superior-Baffled Clearwell at Peak Flow

Calculate 42 min T₁₀ and 58.8 mg·min/L chlorine CT in a 150,000 gal clearwell at 2,500 gpm.

Inputs

Contact segment
mg/L
gal
gpm
mg·min/L
Breakpoint screen
mg/L as N
mg/L as Cl₂

Results

US customary
Achieved CT
58.8 mg·min/L
Effective time T₁₀
42 min
CT / target
1.0691 ×
Theoretical time T
60 min
Contact basinLive diagram
Contact basinFlow path and effective contact time for the selected baffling class. InletOutlet residualBaffling factor 0.7Theoretical time60 minEffective T₁₀42 minCT / target1.0691 ×
Flow path and effective contact time for the selected baffling class.
Breakpoint demand
2.5 mg/L as Cl₂
Dose incl. entered residual
3.9 mg/L as Cl₂

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. Theoretical detention is 150,000 ÷ 2,500 = 60 min. A superior baffling factor of 0.7 gives T₁₀ of 42 min.
  2. The 1.4 mg/L residual gives CT 58.8 mg·min/L, or 1.069 times the entered target of 55.

More worked examples

Equations & conventions

Theoretical and effective time
T = V / Q, T₁₀ = T × BF

Use operating volume and peak flow for the same segment. EPA Table 4-2 uses 0.1, 0.3, 0.5, 0.7 and 1.0 for progressively improved baffling. Use approved tracer results when available.

Disinfection exposure
CT = C × T₁₀, CT ratio = CT / CTrequired

C is the measured disinfectant residual at the end of the segment. Use the applicable required CT for the disinfectant, organism, inactivation goal, temperature and pH.

Theoretical breakpoint
Dᵦ = 7.6 × ammonia-N + other demand

Express ammonia as N and chlorine as Cl₂. The optional residual allowance is added separately. Determine actual breakpoint from site demand testing and approved operating procedures.

Planning basis

A CT ratio at or above one means the calculated value meets your entered target for this segment. A regulated inactivation determination also requires the governing method, sampling, operating envelope and any segment accounting.

Questions

Where should the 1.4 mg/L residual be measured?

Use the chlorine residual at the clearwell outlet corresponding to the relevant peak-flow condition.