WaterTreatLab

Gravity separation / Worked example

Compact Basin with High Overflow Rate

Check a compact rectangular basin at 2.2 MGD with reduced hydraulic detention and high weir loading.

Inputs

Plant & geometry
ft
ft
ft
Hydraulic loading
MGD
ft

Results

US customary
Surface overflow
916.67 gpd/ft² 1.5563 m/h
Detention time
1.9585 h
Weir loading
27,500 gpd/ft 341.53 m³/(m·d)
Settling area
2,400 ft²
Sedimentation basin sectionLive diagram
Sedimentation basin sectionSection profile and hydraulic loading for a single basin. InfluentRectangular basinEffluent weirPlan area2,400 ft²Sidewater depth10 ftWeir loading27,500 gpd/ft
Section profile and hydraulic loading for a single basin.
Review the operating point
  • Surface overflow exceeds the 720 gpd/ft² (0.5 gpm/ft²) reduced-detention screening rate.
  • Detention is below 4 h. Review the applicable Ten States reduced-time conditions with the approving authority.
  • Weir loading exceeds the 20,000 gpd/ft reference for conventional gravity sedimentation.
Active basin volume
179,530 gal

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked solution

These steps walk through the starting inputs in US customary units. Edit the calculator above to test a different operating point.

  1. With 2,400 ft² plan area, SOR is 916.7 gpd/ft², or about 0.637 gpm/ft².
  2. At 10 ft sidewater depth and an 80 ft weir, HRT is about 1.96 h and weir loading is 27,500 gpd/ft.

More worked examples

Equations & conventions

Surface area and volume
A = πD²/4 or L × W, V = A × SWD

Use the plan area and operating sidewater depth. The idealized prism/cylinder excludes volume changes from hoppers, internals and sludge.

Surface overflow and detention
SOR = Q / A, HRT = V / Q

With Q in gal/day and A in ft², SOR is gpd/ft². With V in gal, multiply V/Q by 24 to get hours.

Weir loading
WOR = Q / Lweir

Enter effective, active weir length. Count both contributing launder sides when both accept flow. Use one basin’s flow, area and weir length.

Planning basis

Ten States §4.2.5 gives 4 h conventional water sedimentation, an authority-approved reduced-time pathway at 0.5 gpm/ft² or demonstrated equivalent settling, and 20,000 gpd/ft outlet loading. EPA primary wastewater reference bands are 600–1,200 gpd/ft², 1–4 h and 10,000–20,000 gpd/ft. AWWA M37 covers water clarification design context.

Questions

Which Ten States reduced-time condition is relevant here?

The SOR is above 0.5 gpm/ft². Review the applicable process and any equivalent settling demonstration with the approving authority.