Industrial automation case

PLC chamber stress below operating temperature

A proposed 60 °C chamber setting is below a PLC assembly’s 65 °C use condition. The calculation exposes the direction error.

Inputs

eV
°C
°C
h
0–1
FailStress temperature must exceed use temperature.
Combined AF
0.741761×
Field age
296.704h
Fleet exposure
7,120.91device·h
Upper FIT
323,356

Acceleration by chamber temperature

Acceleration factor versus stress temperatureAcceleration · log₁₀ AF-0.330.1070.5446066.372.779Chamber temperature (°C)TemperatureAF = 1

Both curves share the field temperature and activation energy. The combined curve holds the entered humidity conditions fixed.

Download

Detailed results

Temperature AF
0.7417612 ×
Humidity AF
1 ×
Field age per device
0.03387037 yr
Pooled field exposure
0.8128889 device·yr
Confidence CL
0.9

Raise the chamber temperature above the use condition. The validation status follows the ordering of the temperatures.

Formula trace

  1. AFₜ = exp[(Eₐ / k) (1/Tuse − 1/Tstress)]Use 338.15 K and stress 333.15 K give 0.7417612×.
  2. AFᵣₕ = (RHstress / RHuse)ⁿThe temperature-only model uses AFᵣₕ = 1.
  3. AF = AFₜ AFᵣₕ · Tpool = AF × time × devicesThe chamber run gives 296.7045 h per device and 7,120.907 pooled device-hours.
  4. FITᵤ = 10⁹ [−ln(1−CL)] / TpoolThe upper zero-failure bound is 323,355.6 FIT.

Model assumptions

Equivalent exposure assumes the same failure mechanism at both stress levels. The FIT bound assumes zero failures, a constant rate for that mechanism and pooled exposure from independent devices.

Method and sources