WeibullMTBFLab · Engineering calculation
PLC chamber stress below operating temperature
A proposed 60 °C chamber setting is below a PLC assembly’s 65 °C use condition. The calculation exposes the direction error.
Stress temperature must exceed use temperature.
Inputs
- Stress model
- Arrhenius · temperature
- Activation energy Eₐ
- 0.58 eV
- Use temperature
- 65 °C
- Stress temperature
- 60 °C
- Chamber time per device
- 400 h
- Test devices
- 24
- Confidence CL
- 0.9 0–1
Results
- Combined AF
- 0.7417612 ×
- Field age
- 296.7045 h
- Fleet exposure
- 7,120.907 device·h
- Upper FIT
- 323,355.6
- Temperature AF
- 0.7417612 ×
- Humidity AF
- 1 ×
- Field age per device
- 0.03387037 yr
- Pooled field exposure
- 0.8128889 device·yr
- Confidence CL
- 0.9
AFₜ = exp[(Eₐ / k) (1/Tuse − 1/Tstress)]Use 338.15 K and stress 333.15 K give 0.7417612×.AFᵣₕ = (RHstress / RHuse)ⁿThe temperature-only model uses AFᵣₕ = 1.AF = AFₜ AFᵣₕ · Tpool = AF × time × devicesThe chamber run gives 296.7045 h per device and 7,120.907 pooled device-hours.FITᵤ = 10⁹ [−ln(1−CL)] / TpoolThe upper zero-failure bound is 323,355.6 FIT.
Equivalent exposure assumes the same failure mechanism at both stress levels. The FIT bound assumes zero failures, a constant rate for that mechanism and pooled exposure from independent devices.