Worked example
125-Gallon Reef Summer Chiller BTU/hr and HP
A 125-gallon reef sits in a room that reaches 92 °F. Aim for 78 °F, with 55 W reaching the water from submerged equipment and 40% of a 300 W light fixture as water heat.
See the worked calculationInputs
Results
Edit inputs125-Gallon Reef Summer Chiller BTU/hr and HP
AquariumReefLab spec sheet · https://calcsheetlab.com/aquariumreeflab/guides/125-gallon-reef-summer-chiller-btu-hp/
- Chiller capacity with reserve
- 1,256 BTU/hr
- Heater capacity with reserve
- 153 W
- Cooling-equivalent horsepower
- 0.49 HP
Calculation details
- Winter water-to-air difference
- 12 °F
- Summer air-to-water difference
- 14 °F
- Winter panel and surface transfer
- 124.7 W
- Winter evaporation losses
- 48.1 W
- Summer evaporative cooling
- 37.4 W
- Lighting heat reaching water
- 120 W
- Estimated cold-start time
- 37.5 hr
- Match the BTU/hr capacity at your room temperature and selected water temperature to the chiller’s performance chart.
Input measurements
- Net water volume
- 125 US gal
- Wall material
- Glass
- Inside length
- 72 in
- Inside width
- 18 in
- Water depth
- 22 in
- Wall thickness
- 0.3937 in
- Surface condition
- Open top
- Target water temperature
- 78 °F
- Coldest room temperature
- 66 °F
- Warmest room temperature
- 92 °F
- Winter evaporation
- 0.45 US gal/day
- Summer evaporation
- 0.35 US gal/day
- Pump and equipment heat to water
- 55 W
- Light electrical draw
- 300 W
- Light draw reaching water as heat
- 40 %
- Capacity reserve
- 30 %
Check water temperature with an independent thermometer and verify heater and chiller output in your room before relying on them with livestock.
Worked calculation
These numbers use the original example measurements. The calculator above updates as you edit.
Estimate heat transfer through the wetted area
(2.555 m² × 5.36 W/m²/K) + (0.836 m² × 6 W/m²/K) = 18.7 W/K
The glass wall resistance includes the selected 10 mm thickness. The modeled top is open.
Balance the summer heat
max(0, 145.47 W + 55 W + 120 W − 37.42 W) × 1.3 = 368 W cooling
Multiply by 3.412 to get 1,255.6 BTU/hr. The thermal equivalent is 0.49 HP.
Balance the cold-night heat
max(0, 124.69 W + 48.11 W − 55 W) × 1.3 = 153.1 W
At a 12 °F rise, evaporation adds 1.703 L/day × 28.24 W per L/day of loss.
Frequently asked questions
How does the 125-gallon example count the LED electrical draw?
It counts only the share estimated to heat the water. The fixture can release part of its electricity as heat directly to the surrounding air.
Can I choose a 125-gallon chiller from its advertised tank size alone?
Tank ratings usually assume certain temperatures and equipment loads. Check cooling output at your target water and summer room temperature.