Worked example

125-Gallon Reef Summer Chiller BTU/hr and HP

A 125-gallon reef sits in a room that reaches 92 °F. Aim for 78 °F, with 55 W reaching the water from submerged equipment and 40% of a 300 W light fixture as water heat.

See the worked calculation

Inputs

View results
Tank and temperatures
US gal
in
in
in
in
°F
°F
°F
Evaporation and heat sources
US gal/day

Use observed refill water per day at the cold setting.

US gal/day

Use 0 when cooling credit is unknown.

W

Submerged equipment usually puts most of its watts into the water.

W
%
%
Chiller capacity with reserve
1,256 BTU/hr
Heater capacity with reserve
153 W
Cooling-equivalent horsepower
0.49 HP
Winter and summer heat balanceWinter need 117.8 watts and summer need 283.05 watts before reserve. Winter · lights offHeat loss172.8 WHeat gain55 WSummer · lights onHeat gain320.5 WHeat removed37.4 WCapacity includes 30% reserve.
Winter & summer heat balance

Calculation details

Winter water-to-air difference
12 °F
Summer air-to-water difference
14 °F
Winter panel and surface transfer
124.7 W
Winter evaporation losses
48.1 W
Summer evaporative cooling
37.4 W
Lighting heat reaching water
120 W
Estimated cold-start time
37.5 hr
  • Match the BTU/hr capacity at your room temperature and selected water temperature to the chiller’s performance chart.

Input measurements

Net water volume
125 US gal
Wall material
Glass
Inside length
72 in
Inside width
18 in
Water depth
22 in
Wall thickness
0.3937 in
Surface condition
Open top
Target water temperature
78 °F
Coldest room temperature
66 °F
Warmest room temperature
92 °F
Winter evaporation
0.45 US gal/day
Summer evaporation
0.35 US gal/day
Pump and equipment heat to water
55 W
Light electrical draw
300 W
Light draw reaching water as heat
40 %
Capacity reserve
30 %

Check water temperature with an independent thermometer and verify heater and chiller output in your room before relying on them with livestock.

Worked calculation

These numbers use the original example measurements. The calculator above updates as you edit.

  1. Estimate heat transfer through the wetted area

    (2.555 m² × 5.36 W/m²/K) + (0.836 m² × 6 W/m²/K) = 18.7 W/K

    The glass wall resistance includes the selected 10 mm thickness. The modeled top is open.

  2. Balance the summer heat

    max(0, 145.47 W + 55 W + 120 W − 37.42 W) × 1.3 = 368 W cooling

    Multiply by 3.412 to get 1,255.6 BTU/hr. The thermal equivalent is 0.49 HP.

  3. Balance the cold-night heat

    max(0, 124.69 W + 48.11 W − 55 W) × 1.3 = 153.1 W

    At a 12 °F rise, evaporation adds 1.703 L/day × 28.24 W per L/day of loss.

Frequently asked questions

How does the 125-gallon example count the LED electrical draw?

It counts only the share estimated to heat the water. The fixture can release part of its electricity as heat directly to the surrounding air.

Can I choose a 125-gallon chiller from its advertised tank size alone?

Tank ratings usually assume certain temperatures and equipment loads. Check cooling output at your target water and summer room temperature.