ICCP Transformer-Rectifier Sizing Calculator

Calculate DC operating voltage, select a candidate tap and estimate AC input, annual energy and electricity cost.

Inputs

SI units

Use complete loop cable resistance and an independent estimate of back-EMF. Enter a manufacturer tap to override the example tap list.

A
Ω
Ω
Ω
V
×
V Blank selects the next listed tap.
%
USD/kWh
hr/yr
Required DC
32.85 V
Rated tap
48 V
AC load
1.33 kVA
Annual energy
10,833.54 kWh/yr

Transformer-rectifier circuit

Schematic
Transformer-rectifier circuit (schematic, not to scale)AC supplyRectifierDC loopTransformer / rectifierOPERATING DC32.85 VDESIGN MINIMUM41.06 VSELECTED TAP48 V
Tap covers design voltage

Confirm actual nameplate taps, cable drop, supply and environmental derating before equipment selection.

Design voltage ÷ tap · limit 1.00

Calculation details

Total loop resistance
1 Ω
Minimum design voltage
41.06 V
Operating DC power
1.051 kW
Operating AC real power
1.237 kW
Operating AC apparent power
1.33 kVA
DC load at tap and design current
1.536 kW
AC input at tap and design current
1.943 kVA
Tap headroom over operating voltage
46.12 %
Tap minus design voltage
6.94 V
Annual operating electricity
1,516.7 USD/yr

Method and limits

  1. Build the DC voltage budget

    Required voltage = current × (groundbed + structure + loop cable resistance) + opposing back-EMF. Multiply by the design factor for the minimum design voltage.

  2. Check the tap and AC supply

    Use the first listed tap at or above the design voltage, or enter a nameplate tap. DC kW = operating voltage × current ÷ 1,000. AC kW = DC kW ÷ efficiency. AC kVA = AC kW ÷ power factor. Rated load at the selected tap is shown separately.

  3. Estimate running cost

    AC kW × annual runtime gives kWh/yr. Multiply by the entered tariff for annual cost. Headroom is (tap − operating voltage) ÷ operating voltage.