Crossflow with the higher-capacity stream mixed
The higher-capacity process stream mixes across its flow width while the other stream follows separate passages.
Effectiveness curve
NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)
- Effectiveness
- 71.608%
- Heat duty
- 1,428.7kW
- Hot outlet
- 101.57°C
- Cold outlet
- 117.07°C
- Within the displayed screening checks.
Inputs
Calculated results
- Effectiveness
- 71.608 %
- Actual heat duty
- 1,428.7 kW
- Hot outlet
- 101.57 °C
- Cold outlet
- 117.07 °C
- Number of transfer units
- 2.6163
- Capacity ratio Cᵣ
- 0.58305
- Minimum capacity rate
- 17.2 kW/K
- Maximum possible duty
- 1,995.2 kW
- Difference from ideal duty
- 566.48 kW
Worked solution
Preset calculation · Metric SI
- Divide UA of 45 kW/K by Cₘᵢₙ of 17.2 kW/K to obtain NTU = 2.6163.
- At Cᵣ = 0.58305, the selected arrangement gives 71.608 % effectiveness and 1,428.7 kW actual duty.
- Apply the heat balance to get 101.57 °C at the hot outlet and 117.07 °C at the cold outlet.
Compare duty with the Cₘᵢₙ-mixed option at unchanged UA and check the dashed ideal-counterflow line.
Calculation basis
Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.
Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.
Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.
Methodology and references