Crossflow with the higher-capacity stream mixed

The higher-capacity process stream mixes across its flow width while the other stream follows separate passages.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
71.608%
Heat duty
1,428.7kW
Hot outlet
101.57°C
Cold outlet
117.07°C
Effectiveness curveε EFFECTIVENESSCᵣ 0.58305100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
71.608 %
Actual heat duty
1,428.7 kW
Hot outlet
101.57 °C
Cold outlet
117.07 °C
Number of transfer units
2.6163
Capacity ratio Cᵣ
0.58305
Minimum capacity rate
17.2 kW/K
Maximum possible duty
1,995.2 kW
Difference from ideal duty
566.48 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 45 kW/K by Cₘᵢₙ of 17.2 kW/K to obtain NTU = 2.6163.
  2. At Cᵣ = 0.58305, the selected arrangement gives 71.608 % effectiveness and 1,428.7 kW actual duty.
  3. Apply the heat balance to get 101.57 °C at the hot outlet and 117.07 °C at the cold outlet.

Compare duty with the Cₘᵢₙ-mixed option at unchanged UA and check the dashed ideal-counterflow line.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.