Crossflow with the lower-capacity stream mixed

A baffled liquid side mixes transversely while independent channels keep the higher-capacity stream unmixed.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
76.18%
Heat duty
687.44kW
Hot outlet
45.391°C
Cold outlet
54.974°C
Effectiveness curveε EFFECTIVENESSCᵣ 0.44651100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K
kW/K

Calculated results

Effectiveness
76.18 %
Actual heat duty
687.44 kW
Hot outlet
45.391 °C
Cold outlet
54.974 °C
Number of transfer units
2.2917
Capacity ratio Cᵣ
0.44651
Minimum capacity rate
9.6 kW/K
Maximum possible duty
902.4 kW
Difference from ideal duty
214.96 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 22 kW/K by Cₘᵢₙ of 9.6 kW/K to obtain NTU = 2.2917.
  2. At Cᵣ = 0.44651, the selected arrangement gives 76.18 % effectiveness and 687.44 kW actual duty.
  3. Apply the heat balance to get 45.391 °C at the hot outlet and 54.974 °C at the cold outlet.

The lower heat capacity rate is the hot side here. Swap the two rates to move Cₘᵢₙ to the cold side and recheck the outlets.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.