Isothermal process vapor condenser rating

A condensing process vapor holds an 88 °C temperature while cooling water absorbs the heat.

Effectiveness curve

NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)

Edit inputs ↓
Effectiveness
81.644%
Heat duty
1,697.4kW
Hot outlet
88°C
Cold outlet
75.885°C
Effectiveness curveε EFFECTIVENESSCᵣ 0100%50%004 NTU0% dutyQ / Qmax100% duty
The solid line uses the selected flow pattern. The dashed line shows ideal counterflow at the same capacity ratio.
  • Within the displayed screening checks.

Inputs

°C
°C
kW/K
kW/K

Calculated results

Effectiveness
81.644 %
Actual heat duty
1,697.4 kW
Hot outlet
88 °C
Cold outlet
75.885 °C
Number of transfer units
1.6952
Capacity ratio Cᵣ
0
Minimum capacity rate
31.5 kW/K
Maximum possible duty
2,079 kW
Difference from ideal duty
381.61 kW

Worked solution

Preset calculation · Metric SI

  1. Divide UA of 53.4 kW/K by Cₘᵢₙ of 31.5 kW/K to obtain NTU = 1.6952.
  2. At Cᵣ = 0, the selected arrangement gives 81.644 % effectiveness and 1,697.4 kW actual duty.
  3. Apply the heat balance to get 88 °C at the hot outlet and 75.885 °C at the cold outlet.

Hot outlet stays at 88 °C. Cooling-water capacity and the inlet gap set the maximum duty.

Calculation basis

Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.

Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.

Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.