NPSH Available for a 160°F Hot Water Pump
Compare NPSH available with pump requirements at 160°F, 25 gpm and 8 ft of suction lift.
Inputs
Results
Updates as you editAvailable NPSH meets the entered margin at this duty point.
- Available NPSH
- Entered NPSHr
- Required + margin
The horizontal references hold the duty-point NPSHr and margin fixed. Read NPSHr at each flow for a full curve check.
- Margin above NPSH required
- 4.51 ft
- NPSH required with target margin
- 12 ft
- Available ÷ required
- 1.5
- Site atmospheric pressure
- 14.7 psia
- Water vapor pressure
- 4.747 psia
- Vapor pressure head
- 11.21 ft
- Suction pipe and fitting loss
- 1.98 ft
- Maximum lift at target margin
- 9.51 ft
Inputs
- Design flow
- 25 gpm
- Water temperature
- 160 °F
- Site elevation
- 0 ft
- Suction arrangement
- Suction lift
- Vertical distance to liquid surface
- 8 ft
- Pump NPSH required
- 9 ft
- Target additional NPSH
- 3 ft
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 1½ in nominal
- Suction pipe length
- 30 ft
- 90° elbows
- 2
- Check valves
- 1
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Darcy roughness override
- 0 in
- Local barometric pressure override
- 0 psia
- Vessel gas pressure relative to the site
- 0 psig
Worked calculation
Set the pressure at the liquid surface
Surface pressure = site atmospheric pressure + vessel gauge pressure
The site pressure is 14.7 psia and the liquid surface is at 14.7 psia, equivalent to 34.69 ft of head.
Find water vapor pressure
IAPWS saturation relation: ln(pᵥ/p𝒸) = (T𝒸/T) × Σaᵢ(1 − T/T𝒸)ᵖⁱ
160 °F water has 4.747 psia of vapor pressure, or 11.21 ft of head.
Account for liquid level and suction losses
NPSHa = surface head + signed liquid level − vapor head − suction loss
34.69 ft + (-8 ft) − 11.21 ft − 1.98 ft = 13.51 ft.
Compare with the pump and margin target
Available margin = NPSHa − NPSHr
The available margin is 4.51 ft. The entered NPSHr and margin call for 12 ft total.
What this example shows
At 160°F the vapor pressure consumes a substantial part of the available suction head. Try the colder water case, then compare the worst credible combination of temperature, drawdown and flow.
Frequently asked questions
Why is cavitation more likely at 160°F than at room temperature?
Warmer water has higher vapor pressure. Subtracting that pressure head reduces the available NPSH.
Which temperature belongs in the 160°F suction calculation?
Use the actual liquid temperature at the pump suction, including the hottest credible operating condition.