NPSH Margin for 190°F Water at 5,000 ft
Check a warm recirculation pump near the local boiling point with low atmospheric pressure and a small flooded head.
Inputs
Results
Updates as you editAvailable NPSH exceeds the required value by less than the entered target margin.
- Available NPSH
- Entered NPSHr
- Required + margin
The horizontal references hold the duty-point NPSHr and margin fixed. Read NPSHr at each flow for a full curve check.
- Margin above NPSH required
- 1.01 ft
- NPSH required with target margin
- 11 ft
- Available ÷ required
- 1.13
- Site atmospheric pressure
- 12.23 psia
- Water vapor pressure
- 9.35 psia
- Vapor pressure head
- 22.31 ft
- Suction pipe and fitting loss
- 0.86 ft
- Maximum lift at target margin
- -4.99 ft
Inputs
- Design flow
- 18 gpm
- Water temperature
- 190 °F
- Site elevation
- 5,000 ft
- Suction arrangement
- Flooded suction
- Vertical distance to liquid surface
- 3 ft
- Pump NPSH required
- 8 ft
- Target additional NPSH
- 3 ft
- Pipe material
- Copper Type L
- Nominal pipe size
- 1½ in nominal
- Suction pipe length
- 18 ft
- 90° elbows
- 3
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Darcy roughness override
- 0 in
- Local barometric pressure override
- 0 psia
- Vessel gas pressure relative to the site
- 0 psig
Worked calculation
Set the pressure at the liquid surface
Surface pressure = site atmospheric pressure + vessel gauge pressure
The site pressure is 12.23 psia and the liquid surface is at 12.23 psia, equivalent to 29.18 ft of head.
Find water vapor pressure
IAPWS saturation relation: ln(pᵥ/p𝒸) = (T𝒸/T) × Σaᵢ(1 − T/T𝒸)ᵖⁱ
190 °F water has 9.35 psia of vapor pressure, or 22.31 ft of head.
Account for liquid level and suction losses
NPSHa = surface head + signed liquid level − vapor head − suction loss
29.18 ft + (3 ft) − 22.31 ft − 0.86 ft = 9.01 ft.
Compare with the pump and margin target
Available margin = NPSHa − NPSHr
The available margin is 1.01 ft. The entered NPSHr and margin call for 11 ft total.
What this example shows
At high temperature and altitude, the vapor and atmospheric heads can be close. The result is sensitive to changes in temperature and level.
Frequently asked questions
What does a negative maximum lift mean for this hot loop?
At the target margin the pump requires positive flooded head. The magnitude gives the modeled additional elevation needed at that flow.
Why does altitude matter more for a vented warm loop?
Atmospheric pressure sets the surface pressure directly. Hot water’s vapor pressure still subtracts from that lower absolute pressure.