Pump suction

NPSH Margin for 190°F Water at 5,000 ft

Check a warm recirculation pump near the local boiling point with low atmospheric pressure and a small flooded head.

Inputs

NPSH available9.01 ft

Site and suction duty

gpm
°F
ft
ftUse the low operating water level relative to the pump centerline.
ftRead at actual flow and speed on the pump curve.
ft

Suction pipe and fittings

ftMeasure along the pipe, including vertical runs.
K = 0.9 each for this estimate.
K = 2.5 each for this estimate.
Sum the K values for other fittings.
inEnter 0 to use the nominal-size table.
inEnter 0 to use the material preset.
Surface pressure
psiaEnter 0 to use the elevation estimate.
psigEnter 0 for a vessel vented to atmosphere.

Results

Updates as you edit
NPSH available9.01 ft

Available NPSH exceeds the required value by less than the entered target margin.

Available NPSH versus flow
Available NPSH versus flowThe horizontal references hold the duty-point NPSHr and margin fixed. Read NPSHr at each flow for a full curve check.05.410.816.221.62703.036.059.0812.1Suction flow (gpm)NPSH (ft)Entered duty · 9.01 ft
  • Available NPSH
  • Entered NPSHr
  • Required + margin

The horizontal references hold the duty-point NPSHr and margin fixed. Read NPSHr at each flow for a full curve check.

Margin above NPSH required
1.01 ft
NPSH required with target margin
11 ft
Available ÷ required
1.13
Site atmospheric pressure
12.23 psia
Water vapor pressure
9.35 psia
Vapor pressure head
22.31 ft
Suction pipe and fitting loss
0.86 ft
Maximum lift at target margin
-4.99 ft

Worked calculation

  1. Set the pressure at the liquid surface

    Surface pressure = site atmospheric pressure + vessel gauge pressure

    The site pressure is 12.23 psia and the liquid surface is at 12.23 psia, equivalent to 29.18 ft of head.

  2. Find water vapor pressure

    IAPWS saturation relation: ln(pᵥ/p𝒸) = (T𝒸/T) × Σaᵢ(1 − T/T𝒸)ᵖⁱ

    190 °F water has 9.35 psia of vapor pressure, or 22.31 ft of head.

  3. Account for liquid level and suction losses

    NPSHa = surface head + signed liquid level − vapor head − suction loss

    29.18 ft + (3 ft) − 22.31 ft − 0.86 ft = 9.01 ft.

  4. Compare with the pump and margin target

    Available margin = NPSHa − NPSHr

    The available margin is 1.01 ft. The entered NPSHr and margin call for 11 ft total.

What this example shows

At high temperature and altitude, the vapor and atmospheric heads can be close. The result is sensitive to changes in temperature and level.

Frequently asked questions

What does a negative maximum lift mean for this hot loop?

At the target margin the pump requires positive flooded head. The magnitude gives the modeled additional elevation needed at that flow.

Why does altitude matter more for a vented warm loop?

Atmospheric pressure sets the surface pressure directly. Hot water’s vapor pressure still subtracts from that lower absolute pressure.