Flooded-Suction NPSH from a Vented Reservoir
Check NPSH for a 60 gpm pump with the reservoir water level 6 ft above its centerline.
Inputs
Results
Updates as you editAvailable NPSH meets the entered margin at this duty point.
- Available NPSH
- Entered NPSHr
- Required + margin
The horizontal references hold the duty-point NPSHr and margin fixed. Read NPSHr at each flow for a full curve check.
- Margin above NPSH required
- 26.12 ft
- NPSH required with target margin
- 16 ft
- Available ÷ required
- 3.18
- Site atmospheric pressure
- 14.7 psia
- Water vapor pressure
- 0.389 psia
- Vapor pressure head
- 0.9 ft
- Suction pipe and fitting loss
- 0.96 ft
- Maximum lift at target margin
- 16.12 ft
Inputs
- Design flow
- 60 gpm
- Water temperature
- 72 °F
- Site elevation
- 0 ft
- Suction arrangement
- Flooded suction
- Vertical distance to liquid surface
- 6 ft
- Pump NPSH required
- 12 ft
- Target additional NPSH
- 4 ft
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 2½ in nominal
- Suction pipe length
- 22 ft
- 90° elbows
- 2
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Darcy roughness override
- 0 in
- Local barometric pressure override
- 0 psia
- Vessel gas pressure relative to the site
- 0 psig
Worked calculation
Set the pressure at the liquid surface
Surface pressure = site atmospheric pressure + vessel gauge pressure
The site pressure is 14.7 psia and the liquid surface is at 14.7 psia, equivalent to 33.97 ft of head.
Find water vapor pressure
IAPWS saturation relation: ln(pᵥ/p𝒸) = (T𝒸/T) × Σaᵢ(1 − T/T𝒸)ᵖⁱ
72 °F water has 0.389 psia of vapor pressure, or 0.9 ft of head.
Account for liquid level and suction losses
NPSHa = surface head + signed liquid level − vapor head − suction loss
33.97 ft + (6 ft) − 0.9 ft − 0.96 ft = 38.12 ft.
Compare with the pump and margin target
Available margin = NPSHa − NPSHr
The available margin is 26.12 ft. The entered NPSHr and margin call for 16 ft total.
What this example shows
Positive liquid level contributes head. Use the reservoir’s lowest operating water surface for a conservative flooded-suction check.
Frequently asked questions
Why does flooded suction add the reservoir level to NPSH?
The water surface sits above the pump, so elevation increases inlet head before pipe losses.
Does a flooded reservoir guarantee enough NPSH at all flows?
Losses increase with flow and the pump’s required NPSH can also change. Check the full expected operating range.