Pipe Friction Loss & Water Hammer Calculator
Compare Hazen–Williams and Darcy–Weisbach loss, velocity, Reynolds regime and sudden-closure surge.
Inputs
Results
Updates as you editTurbulent flow. Velocity exceeds the 5 ft/s screening threshold for velocity-related wear and surge. Closure falls in the sudden-closure screening range.
- Darcy–Weisbach
- Hazen–Williams
- Comparison · Darcy
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 11.63 ft
- Darcy pressure drop
- 5.12 psi
- Water velocity
- 5.57 ft/s
- Reynolds number
- 45,064
- Darcy friction factor
- 0.02147
- Fitting head loss
- 0 ft
- Pipe inside diameter
- 1.049 in
- Comparison Darcy loss
- 3.19 ft
- Comparison Hazen–Williams loss
- 3.06 ft
- Comparison velocity
- 3.22 ft/s
- Comparison inside diameter
- 1.38 in
- Sudden-closure pressure rise
- 82.39 psi
- Initial pressure + sudden-closure rise
- 127.39 psig
- Wave round-trip time
- 0.1818 s
Inputs
- Design flow
- 15 gpm
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 1 in nominal
- Developed pipe length
- 100 ft
- Water temperature
- 68 °F
- Compare with size
- 1¼ in nominal
- Comparison material
- Same as primary
- 90° elbows
- 0
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Pressure wave speed
- 1,100 ft/s
- Valve closure time
- 0.1 s
- Velocity arrested
- 100 %
- Initial line pressure
- 45 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
15 gpm in a 1.049 in bore gives 5.57 ft/s. Re = 45,064 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 100 ft, Darcy gives 11.84 ft and Hazen–Williams gives 11.63 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 0 and adds 0 ft. Total Darcy loss is 11.84 ft. The comparison bore gives 3.19 ft at the same flow.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 5.57 ft/s and the wave speed is 1,100 ft/s. The pressure rise estimate is 82.39 psi with a round-trip time of 0.1818 s.
Model and assumptions
Select material and actual bore
Preset bores represent typical pipe dimensions. Hazen–Williams uses C and was developed for turbulent water flow. Darcy uses Reynolds number and relative roughness. The friction factor uses 64/Re in laminar flow, Swamee–Jain in turbulent flow and a smooth blend from Re 2,000 to 4,000.
Screen a pressure transient
The sudden-closure calculation uses a prescribed wave speed and velocity change. Slow, staged or reflective networks require a transient model. The 5 and 8 ft/s velocity thresholds are screening values and allowable velocity depends on the material and service.
Engineering references
Frequently asked questions
When should I prefer Darcy–Weisbach to Hazen–Williams?
Use Darcy when viscosity or flow regime matters. Hazen–Williams is a practical empirical estimate for water in a typical turbulent distribution line.
Is the sudden-closure pressure rise the same as maximum line pressure?
It is an incremental rise. The tool also shows initial pressure plus that rise for the entered starting point. A real network can reflect waves and change the peak.