Piping hydraulics

Pipe Friction Loss & Water Hammer Calculator

Compare Hazen–Williams and Darcy–Weisbach loss, velocity, Reynolds regime and sudden-closure surge.

Inputs

Darcy total head loss11.84 ft

Pipe and flow

gpm
ftMeasure along the pipe, including vertical runs.
°F
Same as primary carries through its C and roughness settings.
Fittings and pipe overrides
K = 0.9 each for this estimate.
K = 2.5 each for this estimate.
Sum the K values for other fittings.
inEnter 0 to use the nominal-size table.
Enter 0 to use the material preset.
inEnter 0 to use the material preset.

Water hammer inputs

ft/sUse a pipe-specific wave speed where available.
s
%
psig

Results

Updates as you edit
Darcy total head loss11.84 ft

Turbulent flow. Velocity exceeds the 5 ft/s screening threshold for velocity-related wear and surge. Closure falls in the sudden-closure screening range.

Head loss versus flow
Head loss versus flowEach curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.04.5913.51822.506.7813.5520.3327.11Flow (gpm)Total loss (ft)Design flow · 11.84 ft
  • Darcy–Weisbach
  • Hazen–Williams
  • Comparison · Darcy

Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.

Hazen–Williams total head loss
11.63 ft
Darcy pressure drop
5.12 psi
Water velocity
5.57 ft/s
Reynolds number
45,064
Darcy friction factor
0.02147
Fitting head loss
0 ft
Pipe inside diameter
1.049 in
Comparison Darcy loss
3.19 ft
Comparison Hazen–Williams loss
3.06 ft
Comparison velocity
3.22 ft/s
Comparison inside diameter
1.38 in
Sudden-closure pressure rise
82.39 psi
Initial pressure + sudden-closure rise
127.39 psig
Wave round-trip time
0.1818 s

Worked calculation

  1. Find velocity and flow regime

    v = Q/A. Re = ρvD/μ.

    15 gpm in a 1.049 in bore gives 5.57 ft/s. Re = 45,064 (turbulent).

  2. Calculate straight-pipe loss two ways

    Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.

    Across 100 ft, Darcy gives 11.84 ft and Hazen–Williams gives 11.63 ft.

  3. Add fitting losses

    Hₖ = ΣK v²/(2g)

    Total K is 0 and adds 0 ft. Total Darcy loss is 11.84 ft. The comparison bore gives 3.19 ft at the same flow.

  4. Screen surge from a sudden change in flow

    Δp = ρaΔv. Wave round-trip time = 2L/a.

    The arrested velocity is 5.57 ft/s and the wave speed is 1,100 ft/s. The pressure rise estimate is 82.39 psi with a round-trip time of 0.1818 s.

Model and assumptions

Select material and actual bore

Preset bores represent typical pipe dimensions. Hazen–Williams uses C and was developed for turbulent water flow. Darcy uses Reynolds number and relative roughness. The friction factor uses 64/Re in laminar flow, Swamee–Jain in turbulent flow and a smooth blend from Re 2,000 to 4,000.

Screen a pressure transient

The sudden-closure calculation uses a prescribed wave speed and velocity change. Slow, staged or reflective networks require a transient model. The 5 and 8 ft/s velocity thresholds are screening values and allowable velocity depends on the material and service.

Engineering references

Frequently asked questions

When should I prefer Darcy–Weisbach to Hazen–Williams?

Use Darcy when viscosity or flow regime matters. Hazen–Williams is a practical empirical estimate for water in a typical turbulent distribution line.

Is the sudden-closure pressure rise the same as maximum line pressure?

It is an incremental rise. The tool also shows initial pressure plus that rise for the entered starting point. A real network can reflect waves and change the peak.