NPSH Loss from a Small Suction Line and Strainer
Estimate suction loss for 32 gpm through a 1¼-inch line with an additional fitting K of 10 for a restricted strainer.
Inputs
Results
Updates as you editAvailable NPSH is below the pump’s required NPSH at this duty point.
- Available NPSH
- Entered NPSHr
- Required + margin
The horizontal references hold the duty-point NPSHr and margin fixed. Read NPSHr at each flow for a full curve check.
- Margin above NPSH required
- -1.36 ft
- NPSH required with target margin
- 14 ft
- Available ÷ required
- 0.86
- Site atmospheric pressure
- 14.7 psia
- Water vapor pressure
- 0.43 psia
- Vapor pressure head
- 0.99 ft
- Suction pipe and fitting loss
- 15.35 ft
- Maximum lift at target margin
- 3.64 ft
Inputs
- Design flow
- 32 gpm
- Water temperature
- 75 °F
- Site elevation
- 0 ft
- Suction arrangement
- Suction lift
- Vertical distance to liquid surface
- 9 ft
- Pump NPSH required
- 10 ft
- Target additional NPSH
- 4 ft
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 1¼ in nominal
- Suction pipe length
- 35 ft
- 90° elbows
- 3
- Check valves
- 1
- Additional fitting K
- 10
- Measured inside diameter
- 0 in
- Darcy roughness override
- 0 in
- Local barometric pressure override
- 0 psia
- Vessel gas pressure relative to the site
- 0 psig
Worked calculation
Set the pressure at the liquid surface
Surface pressure = site atmospheric pressure + vessel gauge pressure
The site pressure is 14.7 psia and the liquid surface is at 14.7 psia, equivalent to 33.99 ft of head.
Find water vapor pressure
IAPWS saturation relation: ln(pᵥ/p𝒸) = (T𝒸/T) × Σaᵢ(1 − T/T𝒸)ᵖⁱ
75 °F water has 0.43 psia of vapor pressure, or 0.99 ft of head.
Account for liquid level and suction losses
NPSHa = surface head + signed liquid level − vapor head − suction loss
33.99 ft + (-9 ft) − 0.99 ft − 15.35 ft = 8.64 ft.
Compare with the pump and margin target
Available margin = NPSHa − NPSHr
The available margin is -1.36 ft. The entered NPSHr and margin call for 14 ft total.
What this example shows
The small line and the restriction consume much of the head. Compare a larger inlet line and use actual clean and fouled strainer pressure drops for design.
Frequently asked questions
Can I enter a measured strainer pressure loss as a fitting K?
Convert the measured loss to head and divide by the pipe velocity head at that flow. Use that K only where the assumption is reasonable.
Why can a clogged strainer cause cavitation with the same tank level?
Extra inlet loss lowers absolute pressure at the pump even while the reservoir level stays constant.