Off-grid pumping

48 V Solar Pump Battery Bank for Night Pumping

Estimate a nominal 48 V battery bank, daily pump energy and PV array for 900 gal/day at 145 ft head.

Inputs

PV array nameplate power323.3 W

Water and sun

gal/day
ft
h/dayDaily solar energy expressed as equivalent full-sun hours.
h/dayUsed to size pump flow and instantaneous power.
%
daysDays of demand to compare for cistern and battery storage.
PV losses and well yield
°FCell temperature during operation.
%/°FPositive magnitude of the module data-sheet coefficient.
%
%
gpmEnter 0 if you do not have a yield test.
Battery assumptions
%
%
%
V

Results

Updates as you edit
PV array nameplate power323.3 W

Battery buffering sizes the PV array by daily energy. Check pump starting load separately.

PV sizing limits
PV sizing limitsThe direct-power bar shows what the array would need to deliver at the design-sun condition without battery power.Daily energy323.3 WDirect power186.7 WSelected array323.3 W

The direct-power bar shows what the array would need to deliver at the design-sun condition without battery power.

Required pump flow
2.14 gpm
Pump electrical demand
136 W
Daily hydraulic energy
0.409 kWh/day
Daily pump electricity
0.952 kWh/day
PV output factor
72.9 %
Energy-limited array
323.3 W
Direct-pumping power floor
186.7 W
Cistern buffer equivalent
1,350 gal
Nominal battery equivalent
1.92 kWh
Battery capacity at bank voltage
40 Ah

Worked calculation

  1. Set the pump duty

    Q = daily volume / hours actually pumping

    900 gal/day in 7 h/day gives 2.14 gpm at 145 ft of TDH.

  2. Find the electrical energy at the pump

    Ewater = ρgVH. Epump = Ewater / wire-to-water efficiency.

    The water needs 0.409 kWh/day. At 43 % efficiency, the pump needs 0.952 kWh/day.

  3. Derate the PV modules

    PV factor = [1 − γ(Tcell − 25 °C)] × (1 − soiling) × (1 − other loss)

    The temperature factor is 88 % and the combined output factor is 72.9 %.

  4. Check daily energy and instantaneous power

    Wenergy = daily pump Wh / (peak sun hours × PV factor × storage efficiency)

    Daily energy gives 323.3 W. Direct pumping needs at least 186.7 W in the design-sun condition. The chosen mode yields 323.3 W.

  5. Allow for storage autonomy

    Cistern = daily volume × days. Nominal battery = pump kWh × days / (usable fraction × discharge efficiency).

    1.5 days gives 1,350 gal of cistern storage or 1.92 kWh of nominal battery capacity.

What this example shows

The array estimate includes round-trip energy loss. The nominal battery uses the allowable discharge fraction and discharge-path efficiency. Check inverter starting and continuous current against the pump.

Frequently asked questions

Why does the 48 V battery need more rated kWh than pump kWh?

Only a fraction of nameplate capacity is used, and delivery to the pump incurs discharge-side losses.

How are amperes and amp-hours different in this bank example?

Amp-hours describe stored charge. The battery and inverter must separately support the pump’s instantaneous running and starting current.