48 V Solar Pump Battery Bank for Night Pumping
Estimate a nominal 48 V battery bank, daily pump energy and PV array for 900 gal/day at 145 ft head.
Inputs
Results
Updates as you editBattery buffering sizes the PV array by daily energy. Check pump starting load separately.
The direct-power bar shows what the array would need to deliver at the design-sun condition without battery power.
- Required pump flow
- 2.14 gpm
- Pump electrical demand
- 136 W
- Daily hydraulic energy
- 0.409 kWh/day
- Daily pump electricity
- 0.952 kWh/day
- PV output factor
- 72.9 %
- Energy-limited array
- 323.3 W
- Direct-pumping power floor
- 186.7 W
- Cistern buffer equivalent
- 1,350 gal
- Nominal battery equivalent
- 1.92 kWh
- Battery capacity at bank voltage
- 40 Ah
Inputs
- Daily water target
- 900 gal/day
- Total dynamic head
- 145 ft
- Peak sun hours
- 4.7 h/day
- Actual pumping window
- 7 h/day
- Wire-to-water efficiency
- 43 %
- Operating mode
- Battery-buffered pump
- Storage autonomy
- 1.5 days
- Design PV cell temperature
- 131 °F
- Power loss per degree
- 0.222 %/°F
- Soiling loss
- 8 %
- Wiring and mismatch loss
- 10 %
- Tested well yield
- 0 gpm
- Battery round-trip efficiency
- 86 %
- Discharge-path efficiency
- 93 %
- Usable depth of discharge
- 80 %
- Battery bank voltage
- 48 V
Worked calculation
Set the pump duty
Q = daily volume / hours actually pumping
900 gal/day in 7 h/day gives 2.14 gpm at 145 ft of TDH.
Find the electrical energy at the pump
Ewater = ρgVH. Epump = Ewater / wire-to-water efficiency.
The water needs 0.409 kWh/day. At 43 % efficiency, the pump needs 0.952 kWh/day.
Derate the PV modules
PV factor = [1 − γ(Tcell − 25 °C)] × (1 − soiling) × (1 − other loss)
The temperature factor is 88 % and the combined output factor is 72.9 %.
Check daily energy and instantaneous power
Wenergy = daily pump Wh / (peak sun hours × PV factor × storage efficiency)
Daily energy gives 323.3 W. Direct pumping needs at least 186.7 W in the design-sun condition. The chosen mode yields 323.3 W.
Allow for storage autonomy
Cistern = daily volume × days. Nominal battery = pump kWh × days / (usable fraction × discharge efficiency).
1.5 days gives 1,350 gal of cistern storage or 1.92 kWh of nominal battery capacity.
What this example shows
The array estimate includes round-trip energy loss. The nominal battery uses the allowable discharge fraction and discharge-path efficiency. Check inverter starting and continuous current against the pump.
Frequently asked questions
Why does the 48 V battery need more rated kWh than pump kWh?
Only a fraction of nameplate capacity is used, and delivery to the pump incurs discharge-side losses.
How are amperes and amp-hours different in this bank example?
Amp-hours describe stored charge. The battery and inverter must separately support the pump’s instantaneous running and starting current.