1-Inch vs 1¼-Inch PVC Friction Loss at 15 GPM
Compare 100 ft of two Schedule 40 PVC sizes at 15 gpm using actual bores, velocity and both loss methods.
Inputs
Results
Updates as you editTurbulent flow. Velocity exceeds the 5 ft/s screening threshold for velocity-related wear and surge. Closure falls in the sudden-closure screening range.
- Darcy–Weisbach
- Hazen–Williams
- Comparison · Darcy
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 11.63 ft
- Darcy pressure drop
- 5.12 psi
- Water velocity
- 5.57 ft/s
- Reynolds number
- 45,064
- Darcy friction factor
- 0.02147
- Fitting head loss
- 0 ft
- Pipe inside diameter
- 1.049 in
- Comparison Darcy loss
- 3.19 ft
- Comparison Hazen–Williams loss
- 3.06 ft
- Comparison velocity
- 3.22 ft/s
- Comparison inside diameter
- 1.38 in
- Sudden-closure pressure rise
- 82.39 psi
- Initial pressure + sudden-closure rise
- 127.39 psig
- Wave round-trip time
- 0.1818 s
Inputs
- Design flow
- 15 gpm
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 1 in nominal
- Developed pipe length
- 100 ft
- Water temperature
- 68 °F
- Compare with size
- 1¼ in nominal
- Comparison material
- Same as primary
- 90° elbows
- 0
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Pressure wave speed
- 1,100 ft/s
- Valve closure time
- 0.1 s
- Velocity arrested
- 100 %
- Initial line pressure
- 45 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
15 gpm in a 1.049 in bore gives 5.57 ft/s. Re = 45,064 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 100 ft, Darcy gives 11.84 ft and Hazen–Williams gives 11.63 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 0 and adds 0 ft. Total Darcy loss is 11.84 ft. The comparison bore gives 3.19 ft at the same flow.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 5.57 ft/s and the wave speed is 1,100 ft/s. The pressure rise estimate is 82.39 psi with a round-trip time of 0.1818 s.
What this example shows
The 1-inch bore carries water above the 5 ft/s screening threshold. The larger bore reduces velocity and head loss. Increase the length to see how straight-pipe loss changes.
Frequently asked questions
Why do 1.049 and 1.380 inches appear for these PVC sizes?
They are the representative inside bores of the nominal 1-inch and 1¼-inch Schedule 40 sizes.
At 15 gpm does a longer straight PVC line increase velocity?
Velocity is set by flow and the inside area. Doubling the length doubles the straight-pipe head loss at constant flow.