Water Hammer in 300 ft of 2-Inch PVC
Screen a fast valve closure on 300 ft of 2-inch PVC at 50 gpm and a 45 psi starting line pressure.
Inputs
Results
Updates as you editTurbulent flow. Velocity is within the 5 ft/s design screening threshold. Closure falls in the sudden-closure screening range.
- Darcy–Weisbach
- Hazen–Williams
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 11.92 ft
- Darcy pressure drop
- 5.1 psi
- Water velocity
- 4.78 ft/s
- Reynolds number
- 76,233
- Darcy friction factor
- 0.01907
- Fitting head loss
- 0 ft
- Pipe inside diameter
- 2.067 in
- Sudden-closure pressure rise
- 77.16 psi
- Initial pressure + sudden-closure rise
- 122.16 psig
- Wave round-trip time
- 0.5 s
Inputs
- Design flow
- 50 gpm
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 2 in nominal
- Developed pipe length
- 300 ft
- Water temperature
- 68 °F
- Compare with size
- No comparison
- 90° elbows
- 0
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Pressure wave speed
- 1,200 ft/s
- Valve closure time
- 0.08 s
- Velocity arrested
- 100 %
- Initial line pressure
- 45 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
50 gpm in a 2.067 in bore gives 4.78 ft/s. Re = 76,233 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 300 ft, Darcy gives 11.8 ft and Hazen–Williams gives 11.92 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 0 and adds 0 ft. Total Darcy loss is 11.8 ft.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 4.78 ft/s and the wave speed is 1,200 ft/s. The pressure rise estimate is 77.16 psi with a round-trip time of 0.5 s.
What this example shows
The 0.08 s valve movement is shorter than the 0.5 s wave round trip in this example. Check the pressure rating against the initial pressure plus the modeled sudden rise.
Frequently asked questions
Which flow value matters for a 2-inch valve that closes partway?
Use the flow before closure and enter the fraction of line velocity arrested, consistent with the expected flow change.
When does this 300 ft water-hammer calculation count a closure as fast?
The screen compares closure time with 2L/a. At 300 ft and 1,200 ft/s, the wave returns in 0.5 seconds.