Piping hydraulics

Water Hammer in 300 ft of 2-Inch PVC

Screen a fast valve closure on 300 ft of 2-inch PVC at 50 gpm and a 45 psi starting line pressure.

Inputs

Darcy total head loss11.8 ft

Pipe and flow

gpm
ftMeasure along the pipe, including vertical runs.
°F
Fittings and pipe overrides
K = 0.9 each for this estimate.
K = 2.5 each for this estimate.
Sum the K values for other fittings.
inEnter 0 to use the nominal-size table.
Enter 0 to use the material preset.
inEnter 0 to use the material preset.

Water hammer inputs

ft/sUse a pipe-specific wave speed where available.
s
%
psig

Results

Updates as you edit
Darcy total head loss11.8 ft

Turbulent flow. Velocity is within the 5 ft/s design screening threshold. Closure falls in the sudden-closure screening range.

Head loss versus flow
Head loss versus flowEach curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.0153045607506.9513.920.8527.79Flow (gpm)Total loss (ft)Design flow · 11.8 ft
  • Darcy–Weisbach
  • Hazen–Williams

Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.

Hazen–Williams total head loss
11.92 ft
Darcy pressure drop
5.1 psi
Water velocity
4.78 ft/s
Reynolds number
76,233
Darcy friction factor
0.01907
Fitting head loss
0 ft
Pipe inside diameter
2.067 in
Sudden-closure pressure rise
77.16 psi
Initial pressure + sudden-closure rise
122.16 psig
Wave round-trip time
0.5 s

Worked calculation

  1. Find velocity and flow regime

    v = Q/A. Re = ρvD/μ.

    50 gpm in a 2.067 in bore gives 4.78 ft/s. Re = 76,233 (turbulent).

  2. Calculate straight-pipe loss two ways

    Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.

    Across 300 ft, Darcy gives 11.8 ft and Hazen–Williams gives 11.92 ft.

  3. Add fitting losses

    Hₖ = ΣK v²/(2g)

    Total K is 0 and adds 0 ft. Total Darcy loss is 11.8 ft.

  4. Screen surge from a sudden change in flow

    Δp = ρaΔv. Wave round-trip time = 2L/a.

    The arrested velocity is 4.78 ft/s and the wave speed is 1,200 ft/s. The pressure rise estimate is 77.16 psi with a round-trip time of 0.5 s.

What this example shows

The 0.08 s valve movement is shorter than the 0.5 s wave round trip in this example. Check the pressure rating against the initial pressure plus the modeled sudden rise.

Frequently asked questions

Which flow value matters for a 2-inch valve that closes partway?

Use the flow before closure and enter the fraction of line velocity arrested, consistent with the expected flow change.

When does this 300 ft water-hammer calculation count a closure as fast?

The screen compares closure time with 2L/a. At 300 ft and 1,200 ft/s, the wave returns in 0.5 seconds.