Piping hydraulics

¾-Inch Type L Copper Velocity and Friction at 10 GPM

Check velocity and loss in 75 ft of ¾-inch Type L copper and compare the same duty in 1-inch Type L.

Inputs

Darcy total head loss19.76 ft

Pipe and flow

gpm
ftMeasure along the pipe, including vertical runs.
°F
Same as primary carries through its C and roughness settings.
Fittings and pipe overrides
K = 0.9 each for this estimate.
K = 2.5 each for this estimate.
Sum the K values for other fittings.
inEnter 0 to use the nominal-size table.
Enter 0 to use the material preset.
inEnter 0 to use the material preset.

Water hammer inputs

ft/sUse a pipe-specific wave speed where available.
s
%
psig

Results

Updates as you edit
Darcy total head loss19.76 ft

Turbulent flow. Velocity exceeds the 5 ft/s screening threshold for velocity-related wear and surge. The Joukowsky value represents an instantaneous stop. The entered line and closure fall outside the sudden-closure range.

Head loss versus flow
Head loss versus flowEach curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.03691215012.7125.4238.1250.83Flow (gpm)Total loss (ft)Design flow · 19.76 ft
  • Darcy–Weisbach
  • Hazen–Williams
  • Comparison · Darcy

Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.

Hazen–Williams total head loss
21.66 ft
Darcy pressure drop
8.55 psi
Water velocity
6.63 ft/s
Reynolds number
40,146
Darcy friction factor
0.0221
Fitting head loss
2.46 ft
Pipe inside diameter
0.785 in
Comparison Darcy loss
5.68 ft
Comparison Hazen–Williams loss
6.08 ft
Comparison velocity
3.89 ft/s
Comparison inside diameter
1.025 in
Sudden-closure pressure rise
356.66 psi
Initial pressure + sudden-closure rise
411.66 psig
Wave round-trip time
0.0375 s

Worked calculation

  1. Find velocity and flow regime

    v = Q/A. Re = ρvD/μ.

    10 gpm in a 0.785 in bore gives 6.63 ft/s. Re = 40,146 (turbulent).

  2. Calculate straight-pipe loss two ways

    Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.

    Across 75 ft, Darcy gives 17.3 ft and Hazen–Williams gives 19.2 ft.

  3. Add fitting losses

    Hₖ = ΣK v²/(2g)

    Total K is 3.6 and adds 2.46 ft. Total Darcy loss is 19.76 ft. The comparison bore gives 5.68 ft at the same flow.

  4. Screen surge from a sudden change in flow

    Δp = ρaΔv. Wave round-trip time = 2L/a.

    The arrested velocity is 6.63 ft/s and the wave speed is 4,000 ft/s. The pressure rise estimate is 356.66 psi with a round-trip time of 0.0375 s.

What this example shows

The small copper bore screens above 5 ft/s at 10 gpm. Consider the application’s permitted velocity and verify the pressure budget at peak demand.

Frequently asked questions

What bore does this ¾-inch Type L copper example use?

The table uses a representative 0.785-inch inside diameter. Type K and Type M wall thicknesses give different bores.

How does a larger copper line affect the pressure surge estimate?

At equal flow and wave speed, the larger bore lowers velocity. The sudden-closure pressure rise falls in proportion to the arrested velocity.