¾-Inch Type L Copper Velocity and Friction at 10 GPM
Check velocity and loss in 75 ft of ¾-inch Type L copper and compare the same duty in 1-inch Type L.
Inputs
Results
Updates as you editTurbulent flow. Velocity exceeds the 5 ft/s screening threshold for velocity-related wear and surge. The Joukowsky value represents an instantaneous stop. The entered line and closure fall outside the sudden-closure range.
- Darcy–Weisbach
- Hazen–Williams
- Comparison · Darcy
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 21.66 ft
- Darcy pressure drop
- 8.55 psi
- Water velocity
- 6.63 ft/s
- Reynolds number
- 40,146
- Darcy friction factor
- 0.0221
- Fitting head loss
- 2.46 ft
- Pipe inside diameter
- 0.785 in
- Comparison Darcy loss
- 5.68 ft
- Comparison Hazen–Williams loss
- 6.08 ft
- Comparison velocity
- 3.89 ft/s
- Comparison inside diameter
- 1.025 in
- Sudden-closure pressure rise
- 356.66 psi
- Initial pressure + sudden-closure rise
- 411.66 psig
- Wave round-trip time
- 0.0375 s
Inputs
- Design flow
- 10 gpm
- Pipe material
- Copper Type L
- Nominal pipe size
- ¾ in nominal
- Developed pipe length
- 75 ft
- Water temperature
- 68 °F
- Compare with size
- 1 in nominal
- Comparison material
- Same as primary
- 90° elbows
- 4
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Pressure wave speed
- 4,000 ft/s
- Valve closure time
- 0.1 s
- Velocity arrested
- 100 %
- Initial line pressure
- 55 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
10 gpm in a 0.785 in bore gives 6.63 ft/s. Re = 40,146 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 75 ft, Darcy gives 17.3 ft and Hazen–Williams gives 19.2 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 3.6 and adds 2.46 ft. Total Darcy loss is 19.76 ft. The comparison bore gives 5.68 ft at the same flow.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 6.63 ft/s and the wave speed is 4,000 ft/s. The pressure rise estimate is 356.66 psi with a round-trip time of 0.0375 s.
What this example shows
The small copper bore screens above 5 ft/s at 10 gpm. Consider the application’s permitted velocity and verify the pressure budget at peak demand.
Frequently asked questions
What bore does this ¾-inch Type L copper example use?
The table uses a representative 0.785-inch inside diameter. Type K and Type M wall thicknesses give different bores.
How does a larger copper line affect the pressure surge estimate?
At equal flow and wave speed, the larger bore lowers velocity. The sudden-closure pressure rise falls in proportion to the arrested velocity.