1-Inch PEX vs Copper Friction at 8 GPM
Compare SDR 9 PEX with Type L copper at equal nominal size over a 120 ft domestic water run.
Inputs
Results
Updates as you editTurbulent flow. Velocity is within the 5 ft/s design screening threshold. Closure falls in the sudden-closure screening range.
- Darcy–Weisbach
- Hazen–Williams
- Comparison · Darcy
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 13.38 ft
- Darcy pressure drop
- 6.04 psi
- Water velocity
- 4.4 ft/s
- Reynolds number
- 29,248
- Darcy friction factor
- 0.02372
- Fitting head loss
- 2.04 ft
- Pipe inside diameter
- 0.862 in
- Comparison Darcy loss
- 6.24 ft
- Comparison Hazen–Williams loss
- 6.56 ft
- Comparison velocity
- 3.11 ft/s
- Comparison inside diameter
- 1.025 in
- Sudden-closure pressure rise
- 65.07 psi
- Initial pressure + sudden-closure rise
- 110.07 psig
- Wave round-trip time
- 0.2182 s
Inputs
- Design flow
- 8 gpm
- Pipe material
- PEX CTS SDR 9
- Nominal pipe size
- 1 in nominal
- Developed pipe length
- 120 ft
- Water temperature
- 68 °F
- Compare with size
- 1 in nominal
- Comparison material
- Copper Type L
- 90° elbows
- 2
- Check valves
- 0
- Additional fitting K
- 5
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Pressure wave speed
- 1,100 ft/s
- Valve closure time
- 0.1 s
- Velocity arrested
- 100 %
- Initial line pressure
- 45 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
8 gpm in a 0.862 in bore gives 4.4 ft/s. Re = 29,248 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 120 ft, Darcy gives 11.91 ft and Hazen–Williams gives 11.34 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 6.8 and adds 2.04 ft. Total Darcy loss is 13.96 ft. The comparison bore gives 6.24 ft at the same flow.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 4.4 ft/s and the wave speed is 1,100 ft/s. The pressure rise estimate is 65.07 psi with a round-trip time of 0.2182 s.
What this example shows
This PEX bore is smaller than the copper bore. For insert fittings, use manufacturer loss data if available and enter an appropriate total fitting K.
Frequently asked questions
Does 1-inch PEX use the same bore as 1-inch Type L copper?
The representative bores here are 0.862 inch for PEX and 1.025 inch for Type L copper. The difference affects velocity and head loss.
How can I account for restrictive insert fittings in the PEX route?
Use the manufacturer’s fitting loss data or an equivalent K referenced to the pipe velocity. Add those losses in the fittings group.