2-Inch HDPE DR 11 Mainline Friction at 40 GPM
Compare a 700 ft HDPE mainline at 40 gpm in nominal 2-inch and 2½-inch IPS DR 11.
Inputs
Results
Updates as you editTurbulent flow. Velocity is within the 5 ft/s design screening threshold. The Joukowsky value represents an instantaneous stop. The entered line and closure fall outside the sudden-closure range.
- Darcy–Weisbach
- Hazen–Williams
- Comparison · Darcy
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 25.91 ft
- Darcy pressure drop
- 11.2 psi
- Water velocity
- 4.33 ft/s
- Reynolds number
- 64,872
- Darcy friction factor
- 0.01974
- Fitting head loss
- 1.05 ft
- Pipe inside diameter
- 1.943 in
- Comparison Darcy loss
- 10.43 ft
- Comparison Hazen–Williams loss
- 10.29 ft
- Comparison velocity
- 2.95 ft/s
- Comparison inside diameter
- 2.352 in
- Sudden-closure pressure rise
- 55.3 psi
- Initial pressure + sudden-closure rise
- 90.3 psig
- Wave round-trip time
- 1.4737 s
Inputs
- Design flow
- 40 gpm
- Pipe material
- HDPE IPS DR 11
- Nominal pipe size
- 2 in nominal
- Developed pipe length
- 700 ft
- Water temperature
- 68 °F
- Compare with size
- 2½ in nominal
- Comparison material
- Same as primary
- 90° elbows
- 4
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Pressure wave speed
- 950 ft/s
- Valve closure time
- 2 s
- Velocity arrested
- 100 %
- Initial line pressure
- 35 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
40 gpm in a 1.943 in bore gives 4.33 ft/s. Re = 64,872 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 700 ft, Darcy gives 24.83 ft and Hazen–Williams gives 24.87 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 3.6 and adds 1.05 ft. Total Darcy loss is 25.88 ft. The comparison bore gives 10.43 ft at the same flow.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 4.33 ft/s and the wave speed is 950 ft/s. The pressure rise estimate is 55.3 psi with a round-trip time of 1.4737 s.
What this example shows
The 700 ft run makes the diameter choice matter even with a modest fitting count. Use the pipe’s own pressure-wave data for a more specific surge screen.
Frequently asked questions
How does PumpPipeLab estimate a DR 11 HDPE bore?
It subtracts two wall thicknesses from the IPS outside diameter, using OD ÷ 11 for each wall. For procurement use the actual product data.
What does the HDPE 2-second closure change in this estimate?
It changes the comparison with wave round-trip time. The displayed pressure rise remains the instantaneous Joukowsky reference.