Piping hydraulics

Pressure Drop in an Aged Galvanized Line at 6 GPM

Model a 95 ft galvanized branch with a 0.73-inch measured bore, C of 88 and an aged roughness allowance.

Inputs

Darcy total head loss29.26 ft

Pipe and flow

gpm
ftMeasure along the pipe, including vertical runs.
°F
Same as primary carries through its C and roughness settings.
Fittings and pipe overrides
K = 0.9 each for this estimate.
K = 2.5 each for this estimate.
Sum the K values for other fittings.
inEnter 0 to use the nominal-size table.
Enter 0 to use the material preset.
inEnter 0 to use the material preset.

Water hammer inputs

ft/sUse a pipe-specific wave speed where available.
s
%
psig

Results

Updates as you edit
Darcy total head loss29.26 ft

Turbulent flow. Velocity is within the 5 ft/s design screening threshold. The Joukowsky value represents an instantaneous stop. The entered line and closure fall outside the sudden-closure range.

Head loss versus flow
Head loss versus flowEach curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.01.83.65.47.29019.2538.557.7577Flow (gpm)Total loss (ft)Design flow · 29.26 ft
  • Darcy–Weisbach
  • Hazen–Williams
  • Comparison · Darcy

Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.

Hazen–Williams total head loss
32.96 ft
Darcy pressure drop
12.66 psi
Water velocity
4.6 ft/s
Reynolds number
25,902
Darcy friction factor
0.05469
Fitting head loss
1.18 ft
Pipe inside diameter
0.73 in
Comparison Darcy loss
7.77 ft
Comparison Hazen–Williams loss
7.29 ft
Comparison velocity
3.61 ft/s
Comparison inside diameter
0.824 in
Sudden-closure pressure rise
241.27 psi
Initial pressure + sudden-closure rise
286.27 psig
Wave round-trip time
0.0487 s

Worked calculation

  1. Find velocity and flow regime

    v = Q/A. Re = ρvD/μ.

    6 gpm in a 0.73 in bore gives 4.6 ft/s. Re = 25,902 (turbulent).

  2. Calculate straight-pipe loss two ways

    Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.

    Across 95 ft, Darcy gives 28.08 ft and Hazen–Williams gives 31.78 ft.

  3. Add fitting losses

    Hₖ = ΣK v²/(2g)

    Total K is 3.6 and adds 1.18 ft. Total Darcy loss is 29.26 ft. The comparison bore gives 7.77 ft at the same flow.

  4. Screen surge from a sudden change in flow

    Δp = ρaΔv. Wave round-trip time = 2L/a.

    The arrested velocity is 4.6 ft/s and the wave speed is 3,900 ft/s. The pressure rise estimate is 241.27 psi with a round-trip time of 0.0487 s.

What this example shows

This comparison applies aged parameters only to the primary pipe. Measure both bore and pressure loss if the estimate will drive a replacement decision.

Frequently asked questions

Why run both Hazen and Darcy on the corroded branch?

They model resistance using different empirical inputs. A field pressure drop helps choose realistic values for each method.

Does the aged roughness override apply to the reference PVC pipe?

The comparison uses the selected reference material’s default C and roughness. The primary side keeps its measured overrides.