Pressure Drop in an Aged Galvanized Line at 6 GPM
Model a 95 ft galvanized branch with a 0.73-inch measured bore, C of 88 and an aged roughness allowance.
Inputs
Results
Updates as you editTurbulent flow. Velocity is within the 5 ft/s design screening threshold. The Joukowsky value represents an instantaneous stop. The entered line and closure fall outside the sudden-closure range.
- Darcy–Weisbach
- Hazen–Williams
- Comparison · Darcy
Each curve includes the entered fitting K. The marker identifies the primary Darcy–Weisbach duty.
- Hazen–Williams total head loss
- 32.96 ft
- Darcy pressure drop
- 12.66 psi
- Water velocity
- 4.6 ft/s
- Reynolds number
- 25,902
- Darcy friction factor
- 0.05469
- Fitting head loss
- 1.18 ft
- Pipe inside diameter
- 0.73 in
- Comparison Darcy loss
- 7.77 ft
- Comparison Hazen–Williams loss
- 7.29 ft
- Comparison velocity
- 3.61 ft/s
- Comparison inside diameter
- 0.824 in
- Sudden-closure pressure rise
- 241.27 psi
- Initial pressure + sudden-closure rise
- 286.27 psig
- Wave round-trip time
- 0.0487 s
Inputs
- Design flow
- 6 gpm
- Pipe material
- Galvanized steel Sch 40
- Nominal pipe size
- ¾ in nominal
- Developed pipe length
- 95 ft
- Water temperature
- 68 °F
- Compare with size
- ¾ in nominal
- Comparison material
- PVC Schedule 40
- 90° elbows
- 4
- Check valves
- 0
- Additional fitting K
- 0
- Measured inside diameter
- 0.73 in
- Hazen–Williams C override
- 88
- Darcy roughness override
- 0.018 in
- Pressure wave speed
- 3,900 ft/s
- Valve closure time
- 0.1 s
- Velocity arrested
- 100 %
- Initial line pressure
- 45 psig
Worked calculation
Find velocity and flow regime
v = Q/A. Re = ρvD/μ.
6 gpm in a 0.73 in bore gives 4.6 ft/s. Re = 25,902 (turbulent).
Calculate straight-pipe loss two ways
Darcy: f(L/D)v²/(2g). Hazen–Williams: 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI.
Across 95 ft, Darcy gives 28.08 ft and Hazen–Williams gives 31.78 ft.
Add fitting losses
Hₖ = ΣK v²/(2g)
Total K is 3.6 and adds 1.18 ft. Total Darcy loss is 29.26 ft. The comparison bore gives 7.77 ft at the same flow.
Screen surge from a sudden change in flow
Δp = ρaΔv. Wave round-trip time = 2L/a.
The arrested velocity is 4.6 ft/s and the wave speed is 3,900 ft/s. The pressure rise estimate is 241.27 psi with a round-trip time of 0.0487 s.
What this example shows
This comparison applies aged parameters only to the primary pipe. Measure both bore and pressure loss if the estimate will drive a replacement decision.
Frequently asked questions
Why run both Hazen and Darcy on the corroded branch?
They model resistance using different empirical inputs. A field pressure drop helps choose realistic values for each method.
Does the aged roughness override apply to the reference PVC pipe?
The comparison uses the selected reference material’s default C and roughness. The primary side keeps its measured overrides.