Power and energy

Brine Pump Horsepower at Specific Gravity 1.12

Compare hydraulic and shaft horsepower for 80 gpm of brine at 95 ft of head and specific gravity 1.12.

Inputs

Electrical input at base speed2.94 kW

Duty and efficiency

gpm
ft
%
%
Hz
Hz
h/day
days
Electricity and fluid
USD/kWh
Use 1.00 for water in this estimate.
%Enter 100% without a drive.

Results

Updates as you edit
Electrical input at base speed2.94 kW

Affinity estimates assume comparable pump efficiency and the same run hours.

Affinity laws at variable speed
Affinity laws at variable speedThe marker shows target-speed power as a share of base power.020406080100027.55582.5110Base speed (%)Base duty (%)Target power · 72.9 %
  • Flow ∝ speed
  • Head ∝ speed²
  • Power ∝ speed³

The marker shows target-speed power as a share of base power.

Hydraulic water power
2.15 hp
Brake power at pump shaft
3.47 hp
Motor electrical input equivalent
3.86 hp
Wire-to-water efficiency
54.7 %
Target-speed flow
72 gpm
Target-speed head
76.95 ft
Target-speed electrical input
2.14 kW
Base annual energy
9,863 kWh
Target annual energy
7,190.1 kWh
Base annual electricity cost
1,183.56 USD
Target annual electricity cost
862.81 USD
Annual cost difference
320.74 USD

Worked calculation

  1. Calculate useful water power

    Pwater = ρgQH

    80 gpm at 95 ft and specific gravity 1.12 requires 2.15 hp of hydraulic work.

  2. Allow for pump, motor and drive losses

    Pbrake = Pwater/ηpump. Pmotor = Pbrake/ηmotor. Pwire = Pmotor/ηdrive.

    The shaft needs 3.47 hp. Motor input is 3.86 hp and electrical input before the drive is 2.94 kW.

  3. Scale to the target frequency

    r = f₂/f₁. Q₂ = Q₁r. H₂ = H₁r². P₂ = P₁r³.

    54 Hz ÷ 60 Hz gives a speed ratio of 0.9. Target input is 2.14 kW.

  4. Estimate annual energy and cost

    Annual kWh = input kW × annual hours. Cost = kWh × tariff.

    12 h/day × 280 days gives 3,360 h per year. The two speeds use 9,863 kWh and 7,190.1 kWh.

What this example shows

At a fixed flow, head and efficiency, power rises in proportion to density. Use process-fluid pump data when viscosity changes the duty or efficiency.

Frequently asked questions

Does 1.12 specific gravity add 12% to shaft power?

At the same flow, head and efficiency, yes. Pressure rise and hydraulic power scale with the density.

Can I apply this brine result to highly viscous fluid?

The arithmetic accepts density only. Use a viscosity-corrected pump curve and efficiency at the actual fluid temperature.