Power and energy

Water Horsepower for 12 GPM at 200 ft of Head

Calculate water horsepower, brake horsepower and electrical demand for a small well duty with no VFD losses.

Inputs

Electrical input at base speed0.99 kW

Duty and efficiency

gpm
ft
%
%
Hz
Hz
h/day
days
Electricity and fluid
USD/kWh
Use 1.00 for water in this estimate.
%Enter 100% without a drive.

Results

Updates as you edit
Electrical input at base speed0.99 kW

Affinity estimates assume comparable pump efficiency and the same run hours.

Affinity laws at variable speed
Affinity laws at variable speedThe marker shows target-speed power as a share of base power.020406080100027.55582.5110Base speed (%)Base duty (%)Target power · 100 %
  • Flow ∝ speed
  • Head ∝ speed²
  • Power ∝ speed³

The marker shows target-speed power as a share of base power.

Hydraulic water power
0.61 hp
Brake power at pump shaft
1.1 hp
Motor electrical input equivalent
1.33 hp
Wire-to-water efficiency
45.7 %
Target-speed flow
12 gpm
Target-speed head
200 ft
Target-speed electrical input
0.99 kW
Base annual energy
1,085.6 kWh
Target annual energy
1,085.6 kWh
Base annual electricity cost
162.84 USD
Target annual electricity cost
162.84 USD
Annual cost difference
0 USD

Worked calculation

  1. Calculate useful water power

    Pwater = ρgQH

    12 gpm at 200 ft and specific gravity 1 requires 0.61 hp of hydraulic work.

  2. Allow for pump, motor and drive losses

    Pbrake = Pwater/ηpump. Pmotor = Pbrake/ηmotor. Pwire = Pmotor/ηdrive.

    The shaft needs 1.1 hp. Motor input is 1.33 hp and electrical input before the drive is 0.99 kW.

  3. Scale to the target frequency

    r = f₂/f₁. Q₂ = Q₁r. H₂ = H₁r². P₂ = P₁r³.

    60 Hz ÷ 60 Hz gives a speed ratio of 1. Target input is 0.99 kW.

  4. Estimate annual energy and cost

    Annual kWh = input kW × annual hours. Cost = kWh × tariff.

    3 h/day × 365 days gives 1,095 h per year. The two speeds use 1,085.6 kWh and 1,085.6 kWh.

What this example shows

The fluid power is about 0.61 hp at this duty. The pump shaft requires more because pump efficiency is 55%. Check the shaft-load curve across the expected flow range before choosing the motor.

Frequently asked questions

Which horsepower figure should I use to compare with a 1.5 HP motor label?

Use brake horsepower at the pump shaft for a direct-coupled motor, then check manufacturer load and service limits.

Why is the utility power higher than the brake horsepower equivalent?

The motor converts electrical input to shaft power with losses. This example uses 83% motor efficiency.