Power and energy

30 Hz Pump Affinity Estimate with a Static-Head Limit

Check the theoretical half-speed duty of a 100 gpm, 160 ft pump when the lift alone may be 55 ft.

Inputs

Electrical input at base speed4.93 kW

Duty and efficiency

gpm
ft
%
%
Hz
Hz
h/day
days
Electricity and fluid
USD/kWh
Use 1.00 for water in this estimate.
%Enter 100% without a drive.

Results

Updates as you edit
Electrical input at base speed4.93 kW

Affinity estimates assume comparable pump efficiency and the same run hours.

Affinity laws at variable speed
Affinity laws at variable speedThe marker shows target-speed power as a share of base power.020406080100027.55582.5110Base speed (%)Base duty (%)Target power · 12.5 %
  • Flow ∝ speed
  • Head ∝ speed²
  • Power ∝ speed³

The marker shows target-speed power as a share of base power.

Hydraulic water power
4.05 hp
Brake power at pump shaft
5.78 hp
Motor electrical input equivalent
6.35 hp
Wire-to-water efficiency
61.2 %
Target-speed flow
50 gpm
Target-speed head
40 ft
Target-speed electrical input
0.62 kW
Base annual energy
9,868.2 kWh
Target annual energy
1,233.5 kWh
Base annual electricity cost
1,381.54 USD
Target annual electricity cost
172.69 USD
Annual cost difference
1,208.85 USD

Worked calculation

  1. Calculate useful water power

    Pwater = ρgQH

    100 gpm at 160 ft and specific gravity 1 requires 4.05 hp of hydraulic work.

  2. Allow for pump, motor and drive losses

    Pbrake = Pwater/ηpump. Pmotor = Pbrake/ηmotor. Pwire = Pmotor/ηdrive.

    The shaft needs 5.78 hp. Motor input is 6.35 hp and electrical input before the drive is 4.93 kW.

  3. Scale to the target frequency

    r = f₂/f₁. Q₂ = Q₁r. H₂ = H₁r². P₂ = P₁r³.

    30 Hz ÷ 60 Hz gives a speed ratio of 0.5. Target input is 0.62 kW.

  4. Estimate annual energy and cost

    Annual kWh = input kW × annual hours. Cost = kWh × tariff.

    10 h/day × 200 days gives 2,000 h per year. The two speeds use 9,868.2 kWh and 1,233.5 kWh.

What this example shows

The target-speed head at the corresponding point is 40 ft. Compare the reduced-speed shutoff head with the 55 ft lift and intersect the full curves to establish actual delivery.

Frequently asked questions

Will half speed always deliver half the water against a 55 ft lift?

The similar point has half the flow and one-quarter of the head. A fixed system lift can shift the actual intersection or eliminate delivery.

Which curve value tells me if the pump can start moving water at 30 Hz?

Compare reduced-speed shutoff head against the static lift and any required residual pressure.