VFD Pump Power Savings from 60 Hz to 45 Hz
Use affinity laws to estimate the change in pump power, delivered head and annual kWh at 75% of base speed.
Inputs
Results
Updates as you editAffinity estimates assume comparable pump efficiency and the same run hours.
- Flow ∝ speed
- Head ∝ speed²
- Power ∝ speed³
The marker shows target-speed power as a share of base power.
- Hydraulic water power
- 1.42 hp
- Brake power at pump shaft
- 2.44 hp
- Motor electrical input equivalent
- 2.77 hp
- Wire-to-water efficiency
- 49.5 %
- Target-speed flow
- 30 gpm
- Target-speed head
- 78.75 ft
- Target-speed electrical input
- 0.9 kW
- Base annual energy
- 4,266.1 kWh
- Target annual energy
- 1,799.8 kWh
- Base annual electricity cost
- 682.58 USD
- Target annual electricity cost
- 287.96 USD
- Annual cost difference
- 394.62 USD
Inputs
- Design flow
- 40 gpm
- Total dynamic head
- 140 ft
- Pump efficiency
- 58 %
- Motor efficiency
- 88 %
- Base frequency
- 60 Hz
- Target frequency
- 45 Hz
- Run time
- 8 h/day
- Operating days per year
- 250 days
- Energy tariff
- 0.16 USD/kWh
- Liquid specific gravity
- 1
- Drive efficiency
- 97 %
Worked calculation
Calculate useful water power
Pwater = ρgQH
40 gpm at 140 ft and specific gravity 1 requires 1.42 hp of hydraulic work.
Allow for pump, motor and drive losses
Pbrake = Pwater/ηpump. Pmotor = Pbrake/ηmotor. Pwire = Pmotor/ηdrive.
The shaft needs 2.44 hp. Motor input is 2.77 hp and electrical input before the drive is 2.13 kW.
Scale to the target frequency
r = f₂/f₁. Q₂ = Q₁r. H₂ = H₁r². P₂ = P₁r³.
45 Hz ÷ 60 Hz gives a speed ratio of 0.75. Target input is 0.9 kW.
Estimate annual energy and cost
Annual kWh = input kW × annual hours. Cost = kWh × tariff.
8 h/day × 250 days gives 2,000 h per year. The two speeds use 4,266.1 kWh and 1,799.8 kWh.
What this example shows
At 45 Hz, the similar duty has 75% of the flow, 56.25% of the head and about 42.19% of the input power. Check that the reduced head still clears the system’s static lift and pressure requirement.
Frequently asked questions
How much of the 60 Hz power remains at 45 Hz?
The idealized power ratio is (45 ÷ 60)³ = 0.421875 with similar efficiency.
How do longer run hours affect the 45 Hz savings?
If the pump must move the same daily volume, a lower flow usually increases run time. Compare kWh with the resulting schedule at each speed.