Power and energy

VFD Pump Power Savings from 60 Hz to 45 Hz

Use affinity laws to estimate the change in pump power, delivered head and annual kWh at 75% of base speed.

Inputs

Electrical input at base speed2.13 kW

Duty and efficiency

gpm
ft
%
%
Hz
Hz
h/day
days
Electricity and fluid
USD/kWh
Use 1.00 for water in this estimate.
%Enter 100% without a drive.

Results

Updates as you edit
Electrical input at base speed2.13 kW

Affinity estimates assume comparable pump efficiency and the same run hours.

Affinity laws at variable speed
Affinity laws at variable speedThe marker shows target-speed power as a share of base power.020406080100027.55582.5110Base speed (%)Base duty (%)Target power · 42.19 %
  • Flow ∝ speed
  • Head ∝ speed²
  • Power ∝ speed³

The marker shows target-speed power as a share of base power.

Hydraulic water power
1.42 hp
Brake power at pump shaft
2.44 hp
Motor electrical input equivalent
2.77 hp
Wire-to-water efficiency
49.5 %
Target-speed flow
30 gpm
Target-speed head
78.75 ft
Target-speed electrical input
0.9 kW
Base annual energy
4,266.1 kWh
Target annual energy
1,799.8 kWh
Base annual electricity cost
682.58 USD
Target annual electricity cost
287.96 USD
Annual cost difference
394.62 USD

Worked calculation

  1. Calculate useful water power

    Pwater = ρgQH

    40 gpm at 140 ft and specific gravity 1 requires 1.42 hp of hydraulic work.

  2. Allow for pump, motor and drive losses

    Pbrake = Pwater/ηpump. Pmotor = Pbrake/ηmotor. Pwire = Pmotor/ηdrive.

    The shaft needs 2.44 hp. Motor input is 2.77 hp and electrical input before the drive is 2.13 kW.

  3. Scale to the target frequency

    r = f₂/f₁. Q₂ = Q₁r. H₂ = H₁r². P₂ = P₁r³.

    45 Hz ÷ 60 Hz gives a speed ratio of 0.75. Target input is 0.9 kW.

  4. Estimate annual energy and cost

    Annual kWh = input kW × annual hours. Cost = kWh × tariff.

    8 h/day × 250 days gives 2,000 h per year. The two speeds use 4,266.1 kWh and 1,799.8 kWh.

What this example shows

At 45 Hz, the similar duty has 75% of the flow, 56.25% of the head and about 42.19% of the input power. Check that the reduced head still clears the system’s static lift and pressure requirement.

Frequently asked questions

How much of the 60 Hz power remains at 45 Hz?

The idealized power ratio is (45 ÷ 60)³ = 0.421875 with similar efficiency.

How do longer run hours affect the 45 Hz savings?

If the pump must move the same daily volume, a lower flow usually increases run time. Compare kWh with the resulting schedule at each speed.