1.5 HP Submersible Well Pump at 200 ft TDH
Work through a 12 gpm well with 30 ft of drawdown and a 31 psi outlet, then check a candidate 1.5 HP pump near 200 ft TDH.
Inputs
Results
Updates as you editThe candidate curve has sufficient head at the target flow.
- System curve
- Entered pump curve
The two-point pump curve is an interpolation. The system curve holds the entered pumping water level fixed.
- Static elevation lift
- 125 ft
- Outlet pressure head
- 71.63 ft
- Darcy straight-pipe loss
- 5.38 ft
- Hazen–Williams straight-pipe loss
- 5.06 ft
- Fitting loss
- 0.54 ft
- Pipe velocity
- 2.57 ft/s
- Pipe inside diameter
- 1.38 in
- Candidate head at target
- 221.84 ft
- Estimated intersection flow
- 14.43 gpm
- Estimated intersection head
- 204.85 ft
Inputs
- Target flow
- 12 gpm
- Static water depth
- 85 ft
- Pumping drawdown
- 30 ft
- Outlet above wellhead
- 10 ft
- Required outlet pressure
- 31 psig
- Pipe material
- PVC Schedule 40
- Nominal pipe size
- 1¼ in nominal
- Developed pipe length
- 250 ft
- Use friction method
- Darcy–Weisbach
- Water temperature
- 68 °F
- 90° elbows
- 3
- Check valves
- 1
- Additional fitting K
- 0
- Measured inside diameter
- 0 in
- Hazen–Williams C override
- 0
- Darcy roughness override
- 0 in
- Shutoff head at zero flow
- 260 ft
- Rated curve flow
- 20 gpm
- Head at rated curve flow
- 154 ft
Worked calculation
Find the pumping water level
Pumping depth = static depth + drawdown
85 ft + 30 ft = 115 ft below the wellhead. The outlet then gives 125 ft of static lift.
Convert delivery pressure to head
Hₚ = p / (ρg)
31 psig gives 71.63 ft of pressure head at the entered water temperature.
Add pipe and fitting losses
H𝒻 = f(L/D) v²/(2g) or 10.67 L(Q/C)¹·⁸⁵² / D⁴·⁸⁷⁰⁴ in SI. Hₖ = ΣK v²/(2g).
At 12 gpm the selected method adds 5.38 ft and fittings add 0.54 ft.
Build the duty point
TDH = static lift + pressure head + straight-pipe loss + fittings
125 ft + 71.63 ft + 5.38 ft + 0.54 ft = 202.54 ft.
Compare with the candidate pump
H(Q) = H₀ − (H₀ − H₁)(Q/Q₁)²
The candidate develops 221.84 ft at 12 gpm, a head difference of 19.3 ft.
What this example shows
The requested duty is just over 200 ft of head. Compare 12 gpm at that head against the specific 1.5 HP model’s published curve and check shaft load with the horsepower calculator.
Frequently asked questions
Can every 1.5 HP submersible pump deliver 12 gpm at 200 ft TDH?
Stage count and impeller design set the curve. Check both flow and head on the published chart for the exact pump model.
Where do the 30 ft of drawdown go in this well calculation?
They add to the 85 ft static water depth, giving a pumping water level 115 ft below the wellhead.